1- 5 Operation modes
At the power on, the Genset is in reset mode. With the buttons you can choose the functioning mode you prefer.
1- 5.1 Automatic mode
Push the AUT button to select this functioning mode.
In case of mains failure the remote start output (J5.4) is activated and is de-activated in the presence of the same. This is the standard logic. It’s
also possible to activate the remote start output in special conditions. For more information see the special functions menu M6.
1- 5.2 Manual mode
In this operative mode, to turn-on the generator (activating the remote start output) you must press KG button. With engine running, you can
manually command the transfer switching with KG and KR buttons. KR, besides transferring the load on mains side, turns off the generator.
Pressing and releasing quickly the KR button, KG is opened and the remote start output is deactivated after the cooling time; keeping pressed for 3
seconds KR button, KG is opened and the generator is stopped immediately.
1- 5.3 Reset mode
The remote start output cannot be activated. If the mains is available it is connected to the load. If you select Reset mode, the alarms are reset and
the remote start output is deactivated. If the cause of the alarm remains, the cause is still present. Push the RESET button to select this functioning
mode.
1- 5.4 Test mode
Manual test: Press the TEST button: the remote start output is activated to test the genset for a programmable time.
a) If activated during MAN mode, the load switching can be controlled only by KG and KR buttons, even if the mains is faulty. Disabling the test (or
after the test time), the controller returns to the previous operation mode.
b) If activated during the AUT mode, the test can be made with or without load, depending on the programming of the test setup (see menu M4.3).
Automatic test: If you programmed an automatic test (see menu M4.3), it will run only if you are in automatic mode. The test can be made with or
without load, depending on the programming of the test setup (see menu M4.3).
1- 5.5 Alarms
In case of alarm, the display shows its description. If more different alarms are detected, they appear individually in sequence. For each alarm it is
available a message that can help to identify the source of the problem. The alarm reset can be made by pressing the RESET button; by this, the
alarm is deleted and the genset goes in Reset mode, preventing accidental generator starting attempts. If the alarm, after reset, still remains on the
display, the cause of the alarm is not removed.