SMS SECTION
FORMAT DESCRIPION
# DATA
CHARACTERS
DATA DESCRIPTION
EAS
[Message type]
3
Message header for ATS Genset
=----------------
=[Generator name]
16
Name of the generator
O=AUTO
O=[Program]
4
Operative mode active (“OFF“-“MAN“-“AUTO”-“TEST”)
,P=000
,P=[Active power kW]
3
Total active power
M237
M[Mains voltage line 1]
3
Mains L1-n voltage
,237
,[Mains voltage line 2]
3
Mains L2-n voltage
,232
,[Mains voltage line 3]
3
Mains L3-n voltage
,49.9
,[Mains frequency]
4
Mains frequency
G=000
G=[Genset voltage line 1]
3
Generator L1-n voltage
,000
,[Genset voltage line 2]
3
Generator L2-n voltage
,000
,[Genset voltage line 3]
3
Generator L3-n voltage
,00.0
,[Genset frequency]
4
Generator frequency
A003.0
A[Load current line 1]
4
Load current L1
,000,0
,[Load current line 2]
4
Load current L2
,000.0
,[Load current line 3]
4
Load current L3
B=14.1V
B=[Battery voltage]V
4
Battery voltage
,h=00000
,h=[Work hours]
5
Total work hours
T=99%
T=[Fuel level]
2
Fuel level percentage (if connected to a genset controller)
%,U=00
%,U=[Oil pressure]
2
Oil pressure (if connected to a genset controller)
MC=ON
[Contactor status]
5
Contactors status:
MC=ON means mains contactor ON
GC=ON means generator contactor ON
C=OFF means both contactors OFF
,Z=00
,Z=[Engine temperature]
3
Engine temperature (if connected to a genset controller)
E0
E[Input I4.4 status]
1
Status of input I4.4 (0=not active, 1=active)
0
[Input I4.5 status]
1
Status of input I4.5 (0=not active, 1=active)
0
[Input I4.6 status]
1
Status of input I4.6 (0=not active, 1=active)
0
[Input I4.7 status]
1
Status of input I4.7 (0=not active, 1=active)
,A0
,A[output O5.8 status]
1
Status of output 5.8 (0=not active, 1=active)
0
[output O5.9 status]
1
Status of output 5.9 (0=not active, 1=active)
0
[output O5.10 status]
1
Status of output 5.10 (0=not active, 1=active)
#41001
#[message ID]
5
Message ID without alarms:
00250 = Power on
00201 = Generator ready
00202 = Engine running
00203 = Engine stopping
00204 = Engine stop successful
00205 = KG on
00206 = KR on
00207 = Auto mode
00208 = Test mode
00209 = Off mode
00210 = Man mode
00211 = Ejp on
00212 = Mains return
00219 = Remote stop
00222 = System info
Message ID with alarms, the first digit is the alarm severity:
1 = Global alarm #1 On
2 = Global alarm #2 On
3 = Global alarm #3 On
4 = Shutdown alarm
The other four digits are the alarm code, if the alarm code is greater
than 20000, than the SMS code will be:
[SMS_alarm_code]=[Alarm_ID]-17000
For example "Emergency stop" alarm code 20032 which is a shutdown
alarm will be reported with the following code:
[Emergency_stop_alarm_code] =
(4*10^5)+(20032-17000) = 43032
,Start failure
,[message text]
16
Message text