2- 6.3 M4.3 - Test setup
POS.
NAME
DESCRIPTION
RANGE OF VALUES
DEFAULT
SETTINGS
A
Start hour
You set the hour of test 1 starting.
0-23
9
B
Start min.
You set the minute of test 1 starting.
0-59
30
C
Test length
You set the length time for the test 1. If O
ff
, test 1 is disabled.
O
ff
-255 [min]
5
D
Start hour
You set the hour of test 2 starting.
0-23
10
E
Start min.
You set the minute of test 2 starting.
0-59
30
F
Test length
You set the length time for the test 2. If O
ff,
test 2 is disabled.
O
ff
-255 [min]
O
ff
G
Test with load
If you set it to ON, during the test, the switching between Mains
and Genset should be done.
On-O
ff
O
ff
H
No remote stop
If ON, during the test the remote stop signal is not considered. If
OFF, if the remote stop signal is active during the test, the engine
is stopped and the test finishes automatically.
On-O
ff
O
f
f
POS.
NAME
DESCRIPTION
-
Sunday
If the tick is present, it enables the daily test on Sunday. If the tick is removed, on this day the test is not
executed.
-
Monday
If the tick is present, it enables the daily test on Monday. If the tick is removed, on this day the test is not
executed.
-
Tuesday
If the tick is present, it enables the daily test on Tuesday. If the tick is removed, on this day the test is not
executed.
-
Wednesday
If the tick is present, it enables the daily test on Wednesday. If the tick is removed, on this day the test is not
executed.
-
Thursday
If the tick is present, it enables the daily test on Thursday. If the tick is removed, on this day the test is not
executed.
-
Friday
If the tick is present, it enables the daily test on Friday. If the tick is removed, on this day the test is not executed.
-
Saturday
If the tick is present, it enables the daily test on Saturday. If the tick is removed, on this day the test is not
executed.