Page 37/44
2- 10.3 M8.3 - Input type
The input type setup permits to select the type of programmable inputs. The inputs I4.4, I4.5, I4.6, I4.7, I4.8 can be programmed as:
Disabled: the input is not active
Digital NO: the input is digital type normally open
Digital NC: the input is digital type normally closed
POS.
NAME
RANGE OF VALUES
DEFAULT SETTINGS
A
I4.4
Disabled – Digital NO – Digital NC
Digital NO
B
I4.5
Disabled – Digital NO – Digital NC
Digital NO
C
I4.6
Disabled – Digital NO – Digital NC
Digital NO
D
I4.7
Disabled – Digital NO – Digital NC
Digital NO
E
I4.8
Disabled – Digital NO – Digital NC
Digital NO
2- 10.4 M8.4 - Output type
The output type setup permits to select the type of programmable outputs.
The outputs O5.8, O5.9, O5.10, O5.11, O5.4, O5.5 can be programmed as:
Disabled: the output is not active
Digital NO: the output is digital type normally open
Digital NC: the output is digital type normally closed
POS.
NAME
RANGE OF VALUES
DEFAULT SETTINGS
A
O5.8
Disabled – Digital NO – Digital NC
Digital NO
B
O5.9
Disabled – Digital NO – Digital NC
Digital NO
C
O5.10
Disabled – Digital NO – Digital NC
Digital NO
D
O5.11
Disabled – Digital NO – Digital NC
Digital NO
E
O5.4
Disabled – Digital NO – Digital NC
Digital NO
F
O5.5
Disabled – Digital NO – Digital NC
Digital NO
2- 10.5 M8.5 - Calibration
The measures setup allows to adjust the measured values for genset and mains voltages and load currents. For each voltage measure it’s possible
to set a calibration offset with steps of 0.1 V. For each current measure the offset is a percentage of the CT ratio, in steps of 0,1 %.
POS.
NAME
RANGE OF VALUES
DEFAULT SETTINGS
A
VL1 Gen
-100 +100 (V/10)
0
B
VL2 Gen
-100 +100 (V/10)
0
C
VL3 Gen
-100 +100 (V/10)
0
D
VL1 Mains
-100 +100 (V/10)
0
E
VL2 Mains
-100 +100 (V/10)
0
F
VL3 Mains
-100 +100 (V/10)
0
G
IL1
50.0 – 150.0 (%)
100
H
IL2
50.0 – 150.0 (%)
100
I
IL3
50.0 – 150.0 (%)
100