![Sifam Tinsley ST 301 ATS Скачать руководство пользователя страница 4](http://html.mh-extra.com/html/sifam-tinsley/st-301-ats/st-301-ats_instruction-manual_1267037004.webp)
Page 4/44
1- 3 Hardware ratings
GENERAL CHARACTERISTICS
Rated voltage Vdc
12Vdc (24Vdc)
Allowed Vdc
from 6Vdc to 33Vdc
Rated voltage Vac
400 Vac
Allowed Vac
Up to 500 Vac
Allowed frequency
From 45 to 75 Hz
Max consumption with backlight
250 mA
Temperature range
-30 °C + 70 °C (electric)
-20 °C + 70 °C (display)
-40 °C + 70 °C (storage)
DISPLAY
128x64 px ; 66x33mm
DIGITAL INPUTS
N°
5
STATIC OUTPUT
N°
6 (2x4A ; 4x2A)
SERIAL COMMUNICATION INTERFACE
Interface type
Serial RS -232
Cable length
< 3 m
Baud rate
Up to 115200 bps
Interface type
Serial RS485
Baud rate
Up to 115200 bps
CONTACTORS RELAYS
N° outputs
2
Type of contacts
1x N.O. genset contactor -
1x N.C. mains contactor
Contatcs capacity
8 A / 250 VAC
LOAD CURRENTS INPUT
N°
3
Measure range
Up to 5A
VOLTAGE INPUTS
N°
8
Input type
Resistive coupling
Rated voltage
230 Vac (L-N) - 400 Vac (L-L)
Measure range
TRMS from 0 to 300 Vac (L-N) - from 0 to 500 Vac (L-L)
ACTIVE POWER MEASURE
Measure type
Instant power integration
HARDWARE
N°Keys
13
N°LED
10
STANDARD REFERENCE
EN55011
EN55016-2-1
EN55016-2-3
EN60068-2-1
EN60068-2-2
EN60068-2-27
EN60068-2-30
EN60068-2-6
EN61000-4-2
EN61000-4-3
EN61000-4-4
EN61000-4-5
EN61000-4-6
EN61000-4-8
EN61000-6-2
EN61000-6-4
HBV Bureau Veritas NR320