6 – 13
Fixed-mounted
breaker
Draw-out
circuit breaker
Disturbance
Possible cause(s)
Remedy
X
X
Circuit breaker cannot be
closed.
Circuit breaker ready to close.
"Ready-to-close" indicator:
1.
Closing coil not energized or
incorrectly energized
Check or apply correct voltage
X
2.
The secondary disconnects
have been removed
Plug in the secondary disconnects
X
Circuit breaker cannot be
moved from the withdrawn
position into the disconnected
position
1.
Racking mechanism of circuit
breaker not in disconnected
(DISCON) position (Check
circuit breaker position indica-
tor)
Rack the mechanism into
disconnected position
(green position indicator)
X
Circuit breaker cannot be fitted
in the guide rails
1.
Factory mounted coding of
circuit breaker and cradle does
not match.
The circuit breaker is not rated for
use in this cradle. Replace with the
proper circuit breaker (permissible
circuit breakers are listed on the
cradle type label).
X
When racking from the discon-
nected into the test position,
the circuit breaker does not
move during the first 6
rotations (approximately)
2.
Not a fault
(functional property)
Continue racking
X
Racking handle cannot be
drawn out
1.
Circuit breaker is closed
Press "OPEN" button and pull
racking handle block out
X
2.
Cubicle door not completely
closed (Locking device as
accessory)
Close cubicle door
X
Racking handle cannot be
pushed in
1.
Racking handle is interlocked
Rack circuit breaker into discon-
nected, test or connected position,
unlatch crank and push it fully in
X
Cubicle door cannot be
opened (door interlock as
accessory)
1.
Closed circuit breaker is
preventing opening of
cubicle door
Open the circuit breaker
X
2.
Circuit breaker in connected
position
Rack circuit breaker into test or
disconnected position
Содержание UL 489
Страница 36: ...5 21 Frame size II 3000 A Frame size III 1 Holes 14 mm 0720 1 0721_nu ...
Страница 63: ...7 2 Horizontal connectors 0733_nu top view ...
Страница 64: ...7 3 Rear vertical connectors 0734_nu top view rear view ...
Страница 65: ...7 4 Front connectors 0736_nu front view top view ...
Страница 66: ...7 5 Front connectors and pressure wire terminals 0737_nu top view front view ...
Страница 67: ...7 6 7 2 Frame size II fixed mounted version 0494 3_nu ...
Страница 68: ...7 7 Class C always 0494 5_nu top view rear view ...
Страница 69: ...7 8 2500 0738_nu LH side view front view ...
Страница 71: ...7 10 7 4 Frame size III fixed mounted version 0495 1_nu LH side view ...
Страница 72: ...7 11 0495 2_nu top view top view ...
Страница 73: ...7 12 0495 3_nu top view rear view ...
Страница 75: ...7 14 7 5 Door cut outs fixed mounted circuit breaker Frame size I 0735_nu ...
Страница 76: ...7 15 Frame size II III 0496_nu ...
Страница 77: ...7 16 7 6 Frame size I draw out version 0745_nu ...
Страница 78: ...7 17 0746_nu rear view top view ...
Страница 79: ...7 18 0747_nu bottom view ...
Страница 80: ...7 19 0748_nu ...
Страница 81: ...7 20 0749_nu ...
Страница 82: ...7 21 7 7 Frame size II draw out version 0490 1_ul ...
Страница 86: ...7 25 7 8 Frame size III draw out version ...
Страница 87: ...7 26 ...
Страница 88: ...7 27 ...
Страница 89: ...7 28 7 9 Door cut outs for draw out circuit breakers Frame size I 0750_nu ...
Страница 91: ...7 30 7 11 External sensor for neutral conductor WLNCT2 ...
Страница 92: ...7 31 WLNCT3 ...
Страница 107: ...9 5 I tripping Ground fault tripping ...
Страница 256: ...15 12 Installing FS II and FS III 1 Socket head cap screw M5 with washer and nut 1 2 3 4 6 5 7 8 Size 4 5 Nm 45 lb in ...
Страница 307: ...22 2 Installing the door sealing frame Not for use with fuse carriages Catalog No Door sealing frame WLDSF 1 2 3 ...
Страница 351: ......