9 – 43
9.1.7
Rating Plug
The Rating Plug defines the rated current I
n
within a certain range for a given circuit breaker frame size.
If a rating plug with a higher current than the maximum permissible circuit breaker rated continuous current is plugged in, the electronic
system of the trip unit recognizes this error and signals it with a flashing T.U. ERROR indicator.
The trip unit ignores the rated current value specified by the incorrect Rating Plug and sets it to the value of the smallest Rating Plug for the
frame size of the relevant circuit breaker.
The same happens if a circuit breaker with frame size III is equipped with a Rating Plug smaller than 800 A.
All set protection parameters are adjusted accordingly.
It is not permitted to operate the trip unit without a Rating Plug. If a circuit breaker is nevertheless started up without a Rating Plug,
the T.U. ERROR indicator will light up and the trip unit settings will default to the lowest possible settings for that frame rating.
Frame size
Rating Plug
Catalog No.
I
II
III
q
q
200 A
WLRP200
q
q
225 A
WLRP225
q
q
250 A
WLRP250
q
q
300 A
WLRP300
q
q
315 A
WLRP315
q
q
350 A
WLRP350
q
q
400 A
WLRP400
q
q
450 A
WLRP450
q
q
500 A
WLRP500
q
q
600 A
WLRP600
q
q
630 A
WLRP630
q
q
700 A
WLRP700
q
q
q
800 A
WLRP800
q
q
q
1000 A
WLRP1000
q
q
q
1200 A
WLRP1200
q
q
q
1250 A
WLRP1250
q
q
q
1600 A
WLRP1600
q
q
q
2000 A
WLRP2000
q
q
2500 A
WLRP2500
q
q
3000 A
WLRP3000
q
3200 A
WLRP3200
q
4000 A
WLRP4000
q
5000 A
WLRP5000
Содержание UL 489
Страница 36: ...5 21 Frame size II 3000 A Frame size III 1 Holes 14 mm 0720 1 0721_nu ...
Страница 63: ...7 2 Horizontal connectors 0733_nu top view ...
Страница 64: ...7 3 Rear vertical connectors 0734_nu top view rear view ...
Страница 65: ...7 4 Front connectors 0736_nu front view top view ...
Страница 66: ...7 5 Front connectors and pressure wire terminals 0737_nu top view front view ...
Страница 67: ...7 6 7 2 Frame size II fixed mounted version 0494 3_nu ...
Страница 68: ...7 7 Class C always 0494 5_nu top view rear view ...
Страница 69: ...7 8 2500 0738_nu LH side view front view ...
Страница 71: ...7 10 7 4 Frame size III fixed mounted version 0495 1_nu LH side view ...
Страница 72: ...7 11 0495 2_nu top view top view ...
Страница 73: ...7 12 0495 3_nu top view rear view ...
Страница 75: ...7 14 7 5 Door cut outs fixed mounted circuit breaker Frame size I 0735_nu ...
Страница 76: ...7 15 Frame size II III 0496_nu ...
Страница 77: ...7 16 7 6 Frame size I draw out version 0745_nu ...
Страница 78: ...7 17 0746_nu rear view top view ...
Страница 79: ...7 18 0747_nu bottom view ...
Страница 80: ...7 19 0748_nu ...
Страница 81: ...7 20 0749_nu ...
Страница 82: ...7 21 7 7 Frame size II draw out version 0490 1_ul ...
Страница 86: ...7 25 7 8 Frame size III draw out version ...
Страница 87: ...7 26 ...
Страница 88: ...7 27 ...
Страница 89: ...7 28 7 9 Door cut outs for draw out circuit breakers Frame size I 0750_nu ...
Страница 91: ...7 30 7 11 External sensor for neutral conductor WLNCT2 ...
Страница 92: ...7 31 WLNCT3 ...
Страница 107: ...9 5 I tripping Ground fault tripping ...
Страница 256: ...15 12 Installing FS II and FS III 1 Socket head cap screw M5 with washer and nut 1 2 3 4 6 5 7 8 Size 4 5 Nm 45 lb in ...
Страница 307: ...22 2 Installing the door sealing frame Not for use with fuse carriages Catalog No Door sealing frame WLDSF 1 2 3 ...
Страница 351: ......