9 – 71
Changing the communication parameters
The communication parameters of the COM16 module can be changed by writing the required parameters (baud rate, serial configuration
and Modbus RTU communication address) in data set 160.
Note: Registers not listed are reserved.
For details on data formats and properties, see "SENTRON WL VL circuit breakers with communication capability MODBUS" manual.
Dataset 160
Communication Parameters
Address: A000
hex, Registers: 36, Access: Read / Write
Register
Byte
HIGH/
LOW
Byte
Description
Data
point
Source
WL
Source
VL
1
Source
VL
2
Format
Length Scaling
40960
0
Header; value 0x00 00 00 00
—
COM16
COM11
COM21
—
32
—
40962
4
HIGH
Reserved
—
—
—
—
—
8
—
5
LOW
Modbus RTU address
5
COM16
COM11
COM21
Unsigned char
8
0
40963
6
HIGH
Basic data type (1, 2 or 3)
6
COM16
COM11
COM21
Unsigned char
8
—
7
LOW
Reserved
—
—
—
—
—
8
—
40964
8
Changeable data points in the
basic data
7
COM16
COM11
COM21
Unsigned char
224
—
40984
48
HIGH
Modbus baud rate
427
COM16
COM11
COM21
Unsigned char
8
—
49
LOW
Modbus parity
428
COM16
COM11
COM21
Unsigned char
8
—
40994
68
HIGH
Property for Byte 49
—
COM16
COM11
COM21
Property byte
8
—
69
LOW
Property for Byte 48
—
COM16
COM11
COM21
Property byte
8
—
40995
70
HIGH
Reserved
—
—
—
—
Property byte
8
—
71
LOW
Property for Byte 5
—
COM16
COM11
COM21
Property byte
8
—
40996
72
HIGH
Property for Byte 6
—
COM16
COM11
COM21
Property byte
8
—
73
LOW
Reserved
—
—
—
—
Property byte
8
—
40997
74
HIGH
Property for Byte 8
—
COM16
COM11
COM21
Property byte
8
—
75
LOW
Reserved
—
—
—
—
Property byte
8
—
78
Total Bytes
Содержание UL 489
Страница 36: ...5 21 Frame size II 3000 A Frame size III 1 Holes 14 mm 0720 1 0721_nu ...
Страница 63: ...7 2 Horizontal connectors 0733_nu top view ...
Страница 64: ...7 3 Rear vertical connectors 0734_nu top view rear view ...
Страница 65: ...7 4 Front connectors 0736_nu front view top view ...
Страница 66: ...7 5 Front connectors and pressure wire terminals 0737_nu top view front view ...
Страница 67: ...7 6 7 2 Frame size II fixed mounted version 0494 3_nu ...
Страница 68: ...7 7 Class C always 0494 5_nu top view rear view ...
Страница 69: ...7 8 2500 0738_nu LH side view front view ...
Страница 71: ...7 10 7 4 Frame size III fixed mounted version 0495 1_nu LH side view ...
Страница 72: ...7 11 0495 2_nu top view top view ...
Страница 73: ...7 12 0495 3_nu top view rear view ...
Страница 75: ...7 14 7 5 Door cut outs fixed mounted circuit breaker Frame size I 0735_nu ...
Страница 76: ...7 15 Frame size II III 0496_nu ...
Страница 77: ...7 16 7 6 Frame size I draw out version 0745_nu ...
Страница 78: ...7 17 0746_nu rear view top view ...
Страница 79: ...7 18 0747_nu bottom view ...
Страница 80: ...7 19 0748_nu ...
Страница 81: ...7 20 0749_nu ...
Страница 82: ...7 21 7 7 Frame size II draw out version 0490 1_ul ...
Страница 86: ...7 25 7 8 Frame size III draw out version ...
Страница 87: ...7 26 ...
Страница 88: ...7 27 ...
Страница 89: ...7 28 7 9 Door cut outs for draw out circuit breakers Frame size I 0750_nu ...
Страница 91: ...7 30 7 11 External sensor for neutral conductor WLNCT2 ...
Страница 92: ...7 31 WLNCT3 ...
Страница 107: ...9 5 I tripping Ground fault tripping ...
Страница 256: ...15 12 Installing FS II and FS III 1 Socket head cap screw M5 with washer and nut 1 2 3 4 6 5 7 8 Size 4 5 Nm 45 lb in ...
Страница 307: ...22 2 Installing the door sealing frame Not for use with fuse carriages Catalog No Door sealing frame WLDSF 1 2 3 ...
Страница 351: ......