9 – 54
9.2
CubicleBUS Modules
9.2.1
System architecture
1)
See communication manual for relay details.
-
AO
: Analog output module
-
BSS
: Breaker Status Sensor for acquisition of signals about the circuit breaker status (always combined with COM module)
-
c
: Internal bus system for interconnection of circuit breaker components and for connection of external
c
modules
-
COM15/16/35
: Communications modules to connect breaker-internal CubicleBUS to external supervisory systems via
PROFIBUS-DP, Modbus RTU, PROFINET IO or Modbus TCP. Always combined with the BSS (Breaker Status Sensor).
-
DI
: Digital input module for capturing the status of ungrounded (potential-free) status signals for the purpose of communicating
them or switching active parameter set (ETU776). A maximum of 2 modules in different configurations can be connected.
-
DO
: Digital output modules with 6 outputs each; a maximum of three modules with different configurations or versions can be
connected
-
ETU
: Electronic trip unit
-
Metering
: Metering function or metering function
PLUS
-
Modbus TCP
: Fieldbus for connection of energy management systems and automation systems
-
Open / Close
: Opening coil and closing coil for opening and closing the circuit breaker via communication
-
PROFIBUS DP/PROFINET IO
: Field bus for connection of automation components
-
Protection
: Protection module
-
TD400
: Test Device; adapter for parameterizing, operating and monitoring the circuit breaker via powerconfig
-
VT
: Voltage transformer
-
ZSI
: Module for zone selective interlocking, must always be connected as the first module
NOTE
The basic functions of the electronic trip units do not require an auxiliary power supply.
To use extended functions of the trip units requiring data exchange via the
c
, an external 24 V DC voltage supply
must be connected.
X6
Close/Open (see Note 1)
PROFIBUS-DP
Modbus RTU
PROFINET IO
Modbus TCP
COM15/16/35
TD400
(see Note 1)
Содержание UL 489
Страница 36: ...5 21 Frame size II 3000 A Frame size III 1 Holes 14 mm 0720 1 0721_nu ...
Страница 63: ...7 2 Horizontal connectors 0733_nu top view ...
Страница 64: ...7 3 Rear vertical connectors 0734_nu top view rear view ...
Страница 65: ...7 4 Front connectors 0736_nu front view top view ...
Страница 66: ...7 5 Front connectors and pressure wire terminals 0737_nu top view front view ...
Страница 67: ...7 6 7 2 Frame size II fixed mounted version 0494 3_nu ...
Страница 68: ...7 7 Class C always 0494 5_nu top view rear view ...
Страница 69: ...7 8 2500 0738_nu LH side view front view ...
Страница 71: ...7 10 7 4 Frame size III fixed mounted version 0495 1_nu LH side view ...
Страница 72: ...7 11 0495 2_nu top view top view ...
Страница 73: ...7 12 0495 3_nu top view rear view ...
Страница 75: ...7 14 7 5 Door cut outs fixed mounted circuit breaker Frame size I 0735_nu ...
Страница 76: ...7 15 Frame size II III 0496_nu ...
Страница 77: ...7 16 7 6 Frame size I draw out version 0745_nu ...
Страница 78: ...7 17 0746_nu rear view top view ...
Страница 79: ...7 18 0747_nu bottom view ...
Страница 80: ...7 19 0748_nu ...
Страница 81: ...7 20 0749_nu ...
Страница 82: ...7 21 7 7 Frame size II draw out version 0490 1_ul ...
Страница 86: ...7 25 7 8 Frame size III draw out version ...
Страница 87: ...7 26 ...
Страница 88: ...7 27 ...
Страница 89: ...7 28 7 9 Door cut outs for draw out circuit breakers Frame size I 0750_nu ...
Страница 91: ...7 30 7 11 External sensor for neutral conductor WLNCT2 ...
Страница 92: ...7 31 WLNCT3 ...
Страница 107: ...9 5 I tripping Ground fault tripping ...
Страница 256: ...15 12 Installing FS II and FS III 1 Socket head cap screw M5 with washer and nut 1 2 3 4 6 5 7 8 Size 4 5 Nm 45 lb in ...
Страница 307: ...22 2 Installing the door sealing frame Not for use with fuse carriages Catalog No Door sealing frame WLDSF 1 2 3 ...
Страница 351: ......