9.2.2.7 Connecting voltage transformers
The metering module ("Meter
PLUS
Function") can be set to expect 3W or 4W (LL/LG) connections and will correct the amplitude and phase
of the signal as necessary.
The parameters on the trip unit must be set as follows:
(1)
VT Primary voltage (100 V ac ... 1200 V ac)
(2)
VT Secondary voltage
(100 V/110 V/120 V)
(3)
VT Connection
(Wye / LG, Delta / LL)
Three VTs must be used at all times.
All three VTs must be rated for the rated LL voltage (e.g. 480 V) and can have either 100 V / 110 V or 120 V secondary rated voltage.
DANGER
Hazardous voltage.
Will cause death, serious personal injury, or equipment damage.
Turn off and lock out all power supplying this equipment before working on this device.
Note:
Required primary and secondary overcurrent protection (fusing) not shown for clarity.
to X8.8
to X8.7
to X8.6
to X8.5
L1
L2
L3
LN
120V/ 3
primary bus
configuration
VT primary
connection
VT primary
connection
3:4W System: Wye (L-N, L-G) Connection
V
L-L
(V
L-L
)/ 3
(V
L-L
)/ 3
Secondary
Primary
(277V)
(69V)
(assuming 480V LL)
V
L-L
(480V)
120V
Metering VT Settings:
Delta/Wye : Delta
VT Primary: 480 (for instance)
VT Secondary: 120 (for instance)
Metering VT Settings:
Delta/Wye : Wye
VT Primary: 480 (for instance)
VT Secondary: 120 (for instance)
primary bus
configuration
69V
√
√
√
Secondary
to X8.8
to X8.7
to X8.6
to X8.5
L1
L2
L3
V
1-2
120V
V
2-3
V
3-1
Primary
V
L-L
3
:
3W System: Delta (L-L) Connection
Rotation: A-C-B
(assuming 480V LL)
(480V)
208V
Secondary
to X8.8
to X8.7
to X8.6
to X8.5
L1
L2
L3
V
1-2
120V
V
2-3
V
3-1
Primary
V
L-L
3
:
3W System: Delta (L-L) Connection
Rotation: A-B-C
(assuming 480V LL)
(480V)
208V
Содержание UL 489
Страница 36: ...5 21 Frame size II 3000 A Frame size III 1 Holes 14 mm 0720 1 0721_nu ...
Страница 63: ...7 2 Horizontal connectors 0733_nu top view ...
Страница 64: ...7 3 Rear vertical connectors 0734_nu top view rear view ...
Страница 65: ...7 4 Front connectors 0736_nu front view top view ...
Страница 66: ...7 5 Front connectors and pressure wire terminals 0737_nu top view front view ...
Страница 67: ...7 6 7 2 Frame size II fixed mounted version 0494 3_nu ...
Страница 68: ...7 7 Class C always 0494 5_nu top view rear view ...
Страница 69: ...7 8 2500 0738_nu LH side view front view ...
Страница 71: ...7 10 7 4 Frame size III fixed mounted version 0495 1_nu LH side view ...
Страница 72: ...7 11 0495 2_nu top view top view ...
Страница 73: ...7 12 0495 3_nu top view rear view ...
Страница 75: ...7 14 7 5 Door cut outs fixed mounted circuit breaker Frame size I 0735_nu ...
Страница 76: ...7 15 Frame size II III 0496_nu ...
Страница 77: ...7 16 7 6 Frame size I draw out version 0745_nu ...
Страница 78: ...7 17 0746_nu rear view top view ...
Страница 79: ...7 18 0747_nu bottom view ...
Страница 80: ...7 19 0748_nu ...
Страница 81: ...7 20 0749_nu ...
Страница 82: ...7 21 7 7 Frame size II draw out version 0490 1_ul ...
Страница 86: ...7 25 7 8 Frame size III draw out version ...
Страница 87: ...7 26 ...
Страница 88: ...7 27 ...
Страница 89: ...7 28 7 9 Door cut outs for draw out circuit breakers Frame size I 0750_nu ...
Страница 91: ...7 30 7 11 External sensor for neutral conductor WLNCT2 ...
Страница 92: ...7 31 WLNCT3 ...
Страница 107: ...9 5 I tripping Ground fault tripping ...
Страница 256: ...15 12 Installing FS II and FS III 1 Socket head cap screw M5 with washer and nut 1 2 3 4 6 5 7 8 Size 4 5 Nm 45 lb in ...
Страница 307: ...22 2 Installing the door sealing frame Not for use with fuse carriages Catalog No Door sealing frame WLDSF 1 2 3 ...
Страница 351: ......