background image

15

Installation Guide / User Manual

 | TPS4-01 Surge Protection Device

Maintenance

SPDs require minimal maintenance. Periodic inspection of 
diagnostic LED indicators ensures proper operation. Clean 
SPD as appropriate.

Troubleshooting & Service

Please contact Siemens Technical Support at 800-333-7421 
for service related issues.

Quality SPDs are designed and tested to withstand severe 
duty. However, there are various electrical anomalies against 
which SPDs cannot protect. These are generally Sustained 
Overvoltages also known as Temporary Overvoltages (TOVs). 
In this context, Sustained Overvoltages may be only a few 
cycles. Failed SPDs tend to be symptoms, not root causes. 
There may be larger issues at play. Regardless of cause,  
SPDs attempt to protect their load until failure.

Bonding or reference to ground problems are the root  
cause of many SPD problems. If the SPD shows problems on 
startup, there is reasonable chance of bonding/grounding/
misapplication issue. Such problems permanently damage 
the SPD. If not corrected, SPD problems will reoccur.

Tip:

 Visually confirm N-G bonding. Be aware that a voltmeter 

measuring N-G can be misleading. For example, N-G voltage 
could read 0V because neutral and ground are at the same 
potential purely by happenstance, not because they are 
bonded. Visually confirm bonding.

Tip:

 Experience indicates that regulation-challenged 

generators can cause Sustained Overvoltages, as well as 
ungrounded generators, and/or usual load transfer systems.

Abnormal N-G Voltage Indicators

This SPD include N-G voltage indicators. If the SPD detects 
excessive N-G voltage, the Red Service LED will blink and the 
Audible Alarm will cycle. This condition requires immediate 
attention as the SPD will fail.

Incorrectly bonded distribution systems damage SPDs.  
If the XO or N-G bonding jumper is not installed, the 
electrical system has no reference to ground. It becomes an 
ungrounded system. Please see previous section regarding 
SPDs on ungrounded systems. Such systems are known to 
eventually produce abnormally high L-G voltages. SPDs will 
attempt to chase this system-level overvoltage abnormality 
until the SPD fails. This effect is accelerated on Wye systems 
where SPDs are designed for grounded systems. (SPDs for 
ungrounded systems generally have higher MCOV to allow 
for L-G voltage fluctuations.) Failures of this nature are not 
defects in the SPDs workmanship or material. This is an 
installation error and is not covered by warranty.

A differential voltage circuit monitors neutral to ground 
voltage. When N-G voltage becomes excessive, an  
amplifier energizes a resistor. Eventually, that resistor  
will overheat and cause thermally sensitive shrink wrap  
to shrink around the resistor. This does not occur on 
transient or instantaneous N-G overvoltages. When the  
SPD is deenergized, the shrink wrap covered resistor  
can be accessed by qualified personnel under the  
display plate cover.

Module Replacement & Service

The module is field replaceable. Service should only be 
performed by qualified persons. Deenergize SPD, confirm 
with appropriate measurement equipment and discharge 
internal capacitance to ground. Mark locations and  
carefully disconnect diagnostic cables, contacts, connecting 
conductors, etc. Remove entire TPS4 unit from the Panel. 
Reinstall  in reverse.

There are no user serviceable parts inside the module. 
Disassembly is not permitted.

Modules may be returned to the factory for factory service, 
qualification and return. Please contact factory at  
800-333-7421 for assistance.

Display Replacement

The display is field replaceable. Service should only be 
performed by qualified persons. Deenergize SPD, confirm 
with appropriate measurement equipment and discharge 
internal capacitance to ground. Mark locations and  
carefully disconnect diagnostic cables, contacts, connecting 
conductors, etc. Unbolt display and replace. Reinstall  
in reverse.

Note that a sealing gasket between the display and the 
enclosure is a key component ensuring weather resistance. 
Replace the gasket whenever the display is removed.

Preventive Maintenance (Inspection & Testing)

Inspection of the TPS4 SPD unit should be performed 
periodically, to maintain reliable system performance and 
continued transient voltage surge protection. The large 
variations in operating conditions encountered by units in 
the field make it difficult to set a fixed maintenance interval, 
but inspections utilizing the built-in diagnostics should be 
performed at least on a weekly or monthly basis.

Corrective Maintenance (Repair)

The Siemens TPS4 unit is designed for years of reliable, 
trouble- free operation. Unfortunately, in an extreme case, 
you may experience an alarm condition. In this event, no 
attempt should be made to repair the TPS4 itself. There are 
no serviceable parts within the unit. Any SPD that requires 
service should be appropriately removed from the electrical 
distribution equipment, and replaced by a new SPD of the 
same model.

Technical Support

800-333-7421

Prior to calling Siemens TPS4 Technical Support for  
assistance or ordering parts, please have the following 
information available:

TPS4 model number: __________________________________  
Manufacture date: ____________________________________  
Date of Purchase: _____________________________________  
Your order number: ___________________________________

Return Shipment:

Contact Siemens Customer Support, 866-663-7324 to  
setup an RMA.

Содержание TPS4-01

Страница 1: ...usa siemens com spd Installation Guide User Manual TPS4 01 and L1 for P1 P2 P3 Panels Surge Protection Devices ...

Страница 2: ...letely installed inspected and tested All conductors must be connected and functional including the neutral if required The voltage rating of the SPD and system must be verified before energizing the SPD Failure to follow these guidelines can lead to abnormally high voltages at the SPD This may cause the SPD to fail The warranty is voided if the SPD is incorrectly installed and or if the neutral c...

Страница 3: ...e to the equipment but does not create a potential for personal injury These instructions do not purport to cover all details or variations in equipment nor to provide for every possible contingency to be met in connection with installation operation or maintenance Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser s purpo...

Страница 4: ...oo Example TPS4C0120X000 SPD for a 208 120V panelboard with a surge current capacity of 200kA per phase and a surge counter option When an option is not selected include a zero 0 in the field Example TPS4CL120X000 SPD for a 208 120V panelboard with a surge current capacity of 200kA per phase and a surge counter option When an option is not selected include a zero 0 in the field TPS4 01 SPD for RP1...

Страница 5: ... normal operation and will only conduct current for a very brief duration upon encountering a transient surge The TPS4 unit contains overcurrent and thermal protection to protect against abnormal overvoltage conditions System Grounding An equipment grounding conductor must be used on all electrical circuits connected to the SPD For the best performance use a single point ground system where the se...

Страница 6: ... captive washer 2 or 3 65 in lb 7 Neutral Lug Wire Connection N A 120 in lb 8 36 8 AWG White Neutral Conductor 1 only 2 tabs for single phase modules Figure 1 Revised P1 Panel 1 2 3 4 5 6 7 8 Figure 2 Revised P1 Panel Phase Tab Detail Step 1 Lock off all power supplying this equipment before working on it Step 2 Attach TPS4 Mounting Plates Item 2 2 Places to TPS4 using 10 32 SEM screws with captiv...

Страница 7: ...riented from left to right A B C A The SPD Phase Tab for Phase A must be located above the panelboard bus for Phase A B The SPD Phase Tab for Phase B must be located above the panelboard bus for Phase B C The SPD Phase Tab for Phase C must be located above the panelboard bus for Phase C Care must be taken when connecting to branch breaker to insure that A B C phase connection sequence is maintaine...

Страница 8: ... the panel base rail so that the TPS4 Line Bus Connectors line up with panel bus mounting toles Slide the unit toward the interior until the four mounting holes line up with the four holes in the base rail Step 7 P2 Panel Fasten unit to the main bus using the P2 Panel Carriage Bolt and Nut with captive washer Item 7 provided w P2 Panel Do not Torque at this time Attach the Mounting Plates item 2 t...

Страница 9: ...lay using a T10 Tamper Resistant Torx bit Retain screws Rotate display pocket 180 degrees Carefully fold ribbon cable below pocket and route to minimize sharp bends and double over cable directly beneath the display pocket Reinstall retained 6 32 tamper resistant screws and torque screws to value listed Table 6 Content for display rotation 1 2 Item Description Qty Torque 1 TPS4 Display re use 1 2 ...

Страница 10: ... When all LED s are green the suppressor is on line and functioning properly If a fault condition occurs the audible alarm will sound the Red Service LED will illuminate and the LED representing the affected phase will extinguish indicating that the unit needs service The audible alarm can be silenced by pressing ALARM SILENCE on the touchpad The audible alarm and Dry Contact can be tested by depr...

Страница 11: ... will be displayed again When the SPD experiences an event the screen saver will be dismissed and will not be displayed again until the event is acknowledged by an operator Main Screen The Main Screen is the starting point for navigating through the SPDs menus The Main Screen will show the logged data for the most recent event as well as the current time and date Pressing the UP or DOWN buttons wi...

Страница 12: ...m to the SPD memory You will automatically be brought back to the Setup Menu Adjust Time Screen The Adjust Time Screen will allow you to set the time of the SPD Use the UP DOWN buttons to adjust the value in the selected field until you have the correct value Pressing the CENTER button will advance the cursor to the next time field Once the Seconds have been set pressing the CENTER button will fin...

Страница 13: ...n Surge Event Screen When the SPD detects a surge event this animation will be shown It will remain on screen until acknowledged by an operator Any subsequent events that occur while the Surge event animation is on screen will be registered and queued for acknowledgment Along with displaying the Surge animation the Audio alarm will sound Pressing the CENTER button will acknowledge the event and cl...

Страница 14: ...round Any subsequent events that occur while the NGF event animation is on screen will be registered and queued for acknowledgment Along with displaying the NGF animation the Audio alarm will sound Pressing the CENTER button will acknowledge the event and clear the alarm state The Main Screen will be showing the details for the NGF The SPD may be exposed to a NGF for several minutes The NGF animat...

Страница 15: ... Eventually that resistor will overheat and cause thermally sensitive shrink wrap to shrink around the resistor This does not occur on transient or instantaneous N G overvoltages When the SPD is deenergized the shrink wrap covered resistor can be accessed by qualified personnel under the display plate cover Module Replacement Service The module is field replaceable Service should only be performed...

Страница 16: ...for any specific application and does not constitute a performance guarantee for any projects Actual results are dependent on variable conditions Accordingly Siemens does not make representations warranties or assurances as to the accuracy currency or completeness of the content contained herein If requested we will provide specific technical data or specifications with respect to any customer s p...

Отзывы: