TPS4-01 Installation Instructions for: 
Lighting Panelboards Revise P1 (RP1)

If model number includes W option suffix, additional 
instructions follow:

The following instructions are for the installation of the 
Siemens TPS4 01 and L1 SPD modules in Siemens Revised P1 
(RP1) lighting panelboards. 

Be aware of differences between the Revised P1  
and Original P1 panelboards. SPDs for Original P1  
and Revised P1 are not interchangeable. Original  
P1 panelboards use TPS3 01 or L1 SPDs, whereas  
Revised P1 panelboards use TPS3 02 or L2 SPDs or 
the new TPS4 01 or L1 SPDs..

To determine if a customer has a Revised P1 panel 
– look at the part number of the interior. If the 
part number ends with “N” or “T” then it is a 
Revised P1. If it does not end in either “N” or  
“T” then it is an Original P1 panel. For example: 
P1E42MC250A is an Original P1 panel and 
P1E42MC250AT is a Revised P1 panel. If it is a 
Revised P1 panel ending in “N” – then there is  
no Subfeed space and no place for an SPD to be 
installed internally. A different SPD like the new 
Bolthshield BSPD product line can be an option  
for the Revised P1 panel ending in “N” because  
it mounts in a unit space.

Item

Description

Qty.

Torque

1

TPS4

1

2

TPS4 Mounting Plate

2

3

#10-32 Hex Screw w/captive washer

4

30 in-lb

4

#10-24 Hex Thread Rolling Screw

4

30 in-lb

5

TPS4 Phase Tabs (part of TPS4 unit)

2* or 3

6

#1/4-20 Hex Screw w/captive washer

2* or 3

65 in-lb

7

Neutral Lug Wire Connection

N/A

120 in-lb

8

36” #8 AWG White Neutral Conductor

1

*only 2 tabs for single phase modules

Figure 1:

  Revised P1 Panel

1

2

3

4

5

6

7

8

Figure 2:

  Revised P1 Panel Phase Tab Detail

Step 1) Lock off all power supplying this equipment before 
working on it.

Step 2) Attach TPS4 Mounting Plates (Item 2, 2 Places) to 
TPS4 using 10- 32 SEM screws with captive lock washers 
(Item 3). The mounting plates should be attached to the 
TPS4 with the offset oriented towards the top of the unit. 
Torque Screws to values listed.

Step 3) Position the TPS4 unit (item 1) on the panel base rail 
so that the TPS4 Phase tabs (Item 5) extend beneath the Bus 
Tabs on RP1 Panel. Attached TPS4 Phase Tabs to Panel Bus 
using #1/4-20 Hex SEM Screws (Item 6). Do not Torque at  
this time.

Step 4) Connect the TPS4 unit to the base rail using four (4)  
of the #10-24 Hex Thread Rolling screws (item 4).

Step 5) If present, connect TPS4 Neutral Connection Lug  
(Item 7) to Panel Neutral using 8 AWG minimum wire.

For best SPD performance, trim wire as required to provide 
shortest possible route between TPS4 Neutral connection 
and Panel Neutral Connection. Route wire as  straight  as  
possible and use  gentle radius on any bends. Do not kink 
wire. Prevent wire from encroaching breaker locations.

Neutral Connection is not applicable on Delta systems.

Step 6) Torque all connections to the values as specified on  
the installation.

Table 3:

   Content for Installation in Lighting Panelboards  

 

Revised P1

6

TPS4-01 Surge Protection Device | 

Installation Guide / User Manual

Содержание TPS4-01

Страница 1: ...usa siemens com spd Installation Guide User Manual TPS4 01 and L1 for P1 P2 P3 Panels Surge Protection Devices ...

Страница 2: ...letely installed inspected and tested All conductors must be connected and functional including the neutral if required The voltage rating of the SPD and system must be verified before energizing the SPD Failure to follow these guidelines can lead to abnormally high voltages at the SPD This may cause the SPD to fail The warranty is voided if the SPD is incorrectly installed and or if the neutral c...

Страница 3: ...e to the equipment but does not create a potential for personal injury These instructions do not purport to cover all details or variations in equipment nor to provide for every possible contingency to be met in connection with installation operation or maintenance Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser s purpo...

Страница 4: ...oo Example TPS4C0120X000 SPD for a 208 120V panelboard with a surge current capacity of 200kA per phase and a surge counter option When an option is not selected include a zero 0 in the field Example TPS4CL120X000 SPD for a 208 120V panelboard with a surge current capacity of 200kA per phase and a surge counter option When an option is not selected include a zero 0 in the field TPS4 01 SPD for RP1...

Страница 5: ... normal operation and will only conduct current for a very brief duration upon encountering a transient surge The TPS4 unit contains overcurrent and thermal protection to protect against abnormal overvoltage conditions System Grounding An equipment grounding conductor must be used on all electrical circuits connected to the SPD For the best performance use a single point ground system where the se...

Страница 6: ... captive washer 2 or 3 65 in lb 7 Neutral Lug Wire Connection N A 120 in lb 8 36 8 AWG White Neutral Conductor 1 only 2 tabs for single phase modules Figure 1 Revised P1 Panel 1 2 3 4 5 6 7 8 Figure 2 Revised P1 Panel Phase Tab Detail Step 1 Lock off all power supplying this equipment before working on it Step 2 Attach TPS4 Mounting Plates Item 2 2 Places to TPS4 using 10 32 SEM screws with captiv...

Страница 7: ...riented from left to right A B C A The SPD Phase Tab for Phase A must be located above the panelboard bus for Phase A B The SPD Phase Tab for Phase B must be located above the panelboard bus for Phase B C The SPD Phase Tab for Phase C must be located above the panelboard bus for Phase C Care must be taken when connecting to branch breaker to insure that A B C phase connection sequence is maintaine...

Страница 8: ... the panel base rail so that the TPS4 Line Bus Connectors line up with panel bus mounting toles Slide the unit toward the interior until the four mounting holes line up with the four holes in the base rail Step 7 P2 Panel Fasten unit to the main bus using the P2 Panel Carriage Bolt and Nut with captive washer Item 7 provided w P2 Panel Do not Torque at this time Attach the Mounting Plates item 2 t...

Страница 9: ...lay using a T10 Tamper Resistant Torx bit Retain screws Rotate display pocket 180 degrees Carefully fold ribbon cable below pocket and route to minimize sharp bends and double over cable directly beneath the display pocket Reinstall retained 6 32 tamper resistant screws and torque screws to value listed Table 6 Content for display rotation 1 2 Item Description Qty Torque 1 TPS4 Display re use 1 2 ...

Страница 10: ... When all LED s are green the suppressor is on line and functioning properly If a fault condition occurs the audible alarm will sound the Red Service LED will illuminate and the LED representing the affected phase will extinguish indicating that the unit needs service The audible alarm can be silenced by pressing ALARM SILENCE on the touchpad The audible alarm and Dry Contact can be tested by depr...

Страница 11: ... will be displayed again When the SPD experiences an event the screen saver will be dismissed and will not be displayed again until the event is acknowledged by an operator Main Screen The Main Screen is the starting point for navigating through the SPDs menus The Main Screen will show the logged data for the most recent event as well as the current time and date Pressing the UP or DOWN buttons wi...

Страница 12: ...m to the SPD memory You will automatically be brought back to the Setup Menu Adjust Time Screen The Adjust Time Screen will allow you to set the time of the SPD Use the UP DOWN buttons to adjust the value in the selected field until you have the correct value Pressing the CENTER button will advance the cursor to the next time field Once the Seconds have been set pressing the CENTER button will fin...

Страница 13: ...n Surge Event Screen When the SPD detects a surge event this animation will be shown It will remain on screen until acknowledged by an operator Any subsequent events that occur while the Surge event animation is on screen will be registered and queued for acknowledgment Along with displaying the Surge animation the Audio alarm will sound Pressing the CENTER button will acknowledge the event and cl...

Страница 14: ...round Any subsequent events that occur while the NGF event animation is on screen will be registered and queued for acknowledgment Along with displaying the NGF animation the Audio alarm will sound Pressing the CENTER button will acknowledge the event and clear the alarm state The Main Screen will be showing the details for the NGF The SPD may be exposed to a NGF for several minutes The NGF animat...

Страница 15: ... Eventually that resistor will overheat and cause thermally sensitive shrink wrap to shrink around the resistor This does not occur on transient or instantaneous N G overvoltages When the SPD is deenergized the shrink wrap covered resistor can be accessed by qualified personnel under the display plate cover Module Replacement Service The module is field replaceable Service should only be performed...

Страница 16: ...for any specific application and does not constitute a performance guarantee for any projects Actual results are dependent on variable conditions Accordingly Siemens does not make representations warranties or assurances as to the accuracy currency or completeness of the content contained herein If requested we will provide specific technical data or specifications with respect to any customer s p...

Отзывы: