Parameters
Value range
Default
Configuration DQ/DI group
(DQ2/DI2/DI3)
● Incremental encoder (A, B phase
shift)
● Timer DI2 with enable input DI3
● Timer DQ2 with enable input DI2
● Use inputs individually
Incremental encoder (A, B
phase shift)
Invert counting direction
(incremental encoder)
● Deactivated
● Activated
Deactivated
Operating mode of the digital output
● Numerator
● Timer DI
● Oversampling
Timer DI
Input delay for the
digital input
● none
● 0.05 ms
● 0.1 ms
● 0.4 ms
● 0.8 ms
0.1 ms
Signal evaluation for the counter
● With rising edge
● With falling edge
With rising edge
Further information
See Manual
ET 200SP TM Timer DIDQ 10x24V technology module.
3.3.4.2
Setting options for TM Timer DIDQ 16x24V technology module
Overview
The following pages provide an overview of the properties of the TM Timer DIDQ 16x24V
technology module and the properties that you can define for the channels. Not all of the
parameters are available depending on the settings.
Parameters
Value range
Default
Basic parameters
Channel configuration of the module
● 0 inputs, 16 outputs
● 3 inputs, 13 outputs
● 4 inputs, 12 outputs
● 8 inputs, 8 outputs
0 inputs, 16 outputs
PWM period for the digital outputs
● 10 ms
● 5 ms
● 2 ms
● 1 ms
● 0.5 ms
● 0.2 ms
10 ms
Configuring
3.3 SIMOTION SCOUT TIA
Technology Modules TM Timer DIDQ for SIMOTION SCOUT and SIMOTION SCOUT TIA
Commissioning Manual, 01/2015
49