Note
If you operating several ET 200SP interface modules and technology modules TM Timer
DIDQ, you must set the isochronous mode at all of the modules.
3.2.4
Configuring I/O channels
3.2.4.1
Setting options for TM Timer DIDQ 10x24V technology module
Overview
The following pages provide an overview of the properties of the TM Timer DIDQ 10x24V
technology module and the properties that you can define for the channels. Not all of the
parameters are available depending on the settings.
Parameters
Value range
Default
Basic parameters
PWM period for the digital outputs
● 10 ms
● 5 ms
● 2 ms
● 1 ms
● 0.5 ms
● 0.2 ms
10 ms
Response to CPU STOP
● Output substitute value
● Keep last value
Output substitute value
Enable diagnostics interrupts
● Deactivated
● Activated
Deactivated
Channel parameters
Configuration DQ/DI group (DQ0/DI0
or DQ1/DI1)
● Timer DQ with enable input
● Use input/output individually
Timer DQ with enable input
Operating mode of the digital output
● Timer DQ
● Oversampling
● Pulse width modulation PWM
Timer DQ
Substitute value for the digital output
● 0
● 1
0
High-speed output (0.1 A)
● Deactivated
● Activated
Activated
Inverting of the input or
output signal
● Deactivated
● Activated
Deactivated
HW enable via the digital input
● Level-controlled
● Edge-controlled
Level-controlled
Configuring
3.2 SIMOTION SCOUT
Technology Modules TM Timer DIDQ for SIMOTION SCOUT and SIMOTION SCOUT TIA
30
Commissioning Manual, 01/2015