Configuring the technology module
In the following example, a channel configuration with 4 inputs and 12 outputs is used for the
TM Timer DIDQ 16x24V technology module.
The input and output addresses are assigned to the process image "Servo".
1. In the "Channel configuration" drop-down list under "Basic parameters", select the setting
"4 inputs, 12 outputs".
Figure 3-19 Basic parameters - channel configuration
2. In the "Process image" drop-down list under "I/O addresses", uncheck the "Servo" setting
for each of the inputs and outputs.
As start address of the input or output, only use addresses higher than 63; otherwise, when
compiling the project, an error message will be output.
Configuring
3.3 SIMOTION SCOUT TIA
Technology Modules TM Timer DIDQ for SIMOTION SCOUT and SIMOTION SCOUT TIA
46