TX-I/O Island Bus
Installation and Commissioning
NOTE:
For Smoke Control applications, the field panel controller must be installed in the
lower half of the enclosure.
The TX-I/O island bus is automatically created by connecting the TX-I/O devices one-
after-another on a DIN rail.
Basic Steps for Connecting Devices to the DIN Rail
1.
Slide out the mounting tabs.
2.
Align the channel on the back of the device with the DIN rail.
3.
Using a flat blade screwdriver, push in each mounting tab until it clips onto the DIN
rail.
1.
Align the I/O module with the Power Supply or Bus Connection Module and slide
the I/O module down over the DIN rail and TX-I/O bus connector.
2.
Push in each mounting tab until it clips onto the DIN rail.
TXIO0064R1
1
2
3
5
4
Connecting Devices to the TX-I/O Island Bus.
Required Tools
Screwdrivers for I/O Modules
The I/O module connection terminals have slotted screws.
No. 1 screwdriver
Shaft diameter maximum 0.18” (4.5 mm)
Minimum shaft length 1” (26 mm); however, 1.6” (40 mm) allows access to the
screws while plug-in module is in the "parked" position.
40
Siemens Industry, Inc.
TALON TX-I/O Modules and Island Bus Technical Reference
588-587
CONFIDENTIAL: For internal use only
4/6/2010