TX-I/O Power Supply and Bus Modules
Supply Terminal Connections
24 Vac supply terminals are fused (replaceable) for Class 2 (24 Vac at 50/60 Hz)
through the TX-I/O Power Supply.
24 Vdc supply terminals are connected in the I/O module, not in the terminal base.
24 Vdc is supplied and overload protected in the TX-I/O Power Supply.
TX-I/O Power Supply Specifications
Dimensions (L × W × D)
3.78” × 3.54” × 2.75”
(96 mm × 90 mm × 70 mm)
TX-I/O Bus Communication
Signal pass-thru
Power Requirements
24 Vac +/-20% input @ 50 or 60 Hz
Power Consumption
(Maximum)
35 VA for DC power supply.
(Does not include the 96 VA for the 24 Vac output.)
Power Output
28.8 W (1.2A at 24 Vdc)
24 Vac Power, TXS1.12F4
1
Output: NEC Class 2, 96 VA max, fused at 4A
Input: Class 1 Power Limited, 150 VA max.
TX-I/O Bus Extension (CS/CD)
164 ft (50 m) total max. using two 14-gauge twisted pair cable
Ambient operating temperature
32°F to +122°F (0°C to 50°C), 5 to 93% rh, non-condensing
UL
UL 864 UUKL Smoke Control Equipment
UL 864 UUKL7 Smoke Control Equipment
UL 916 PAZX
CSA 22.2 No. 205 PAZX7
Agency Compliance
CFR47 Part 15, Class A; CFR47 Part 15, Class B
Australian EMC Framework (C-Tick)
2004/108/EC European EMC Directive (CE)
2006/95/EC European Low Voltage Directive (LVD)
1)
May be used for Smoke Control installations with Smoke Control Listed Enclosures and transformers or service boxes. The line to
the 24 Vac input transformer must not exceed 1000 VA. NEC Class 2 wiring may be used up to 96 VA, and NEC Class 1 Power
Limited wiring must be used above 96 VA and up to 1000 VA.
31
Siemens Industry, Inc.
TALON TX-I/O Modules and Island Bus Technical Reference