TX-I/O Modules
TX-I/O Module Feature Summary
CAUTION
Active inputs and output are permitted on the same module when connected
sensors are powered from that module.
When sensors are externally powered, active inputs and outputs should be on
separate modules.
TX-I/O Module Product Number and Name
TXM1.
8X-ML
TXM1.
8X
TXM1.
8U-ML
TXM1.
8U
TXM1.
8D
TXM1.
16D
TXM1.
6R-M
TXM1.
6R
Function
8 Super
Universal
8 Universal
8 DI
16 DI
6 DO Relay
Local Override
•
•
•
General
LCD Display
•
•
NI 1000 LS
•
•
•
•
PT 1000 385
•
•
•
•
LT 1000 375
•
•
•
•
NTC 10K (w/out diode)
•
•
•
•
NTC 100K
•
•
•
•
0-10 Vdc
•
•
•
•
AI
4-20 mA
•
•
0-10 Vdc
•
•
•
•
AO
4-20 mA
•
1
•
1
Static Contact (NC/NO)
•
•
•
•
•
•
Pulse accumulator
•
•
•
•
•
•
25 Hz Counter (with debouncing)
•
•
•
•
DI
10 Hz Counter (with debouncing)
•
2
•
ON/OFF
•
•
DO
Pulse ON
•
•
1)
4-20 mA functionality is available only point terminations 5-8
2)
10 Hz counter functionality is available only on point terminations 1-8
9
Siemens Industry, Inc.
TALON TX-I/O Modules and Island Bus Technical Reference
588-587
CONFIDENTIAL: For internal use only
4/6/2010