ID
Symbols
Message
Cause/Remedy
St
Safety validation mode
Device is in safety validation mode.
Complete the functional test and confirm that it was successful in the Func‐
tional Safety wizard.
SU
Safety critical device error Acknowledge the error in menu "Functional Safety" and enable Functional
Safety mode.
Acknowledging safety-related errors (Page 168)
If the problem persists, contact Technical Support.
The following symbols are also used on the display and in SIMATIC PDM.
Display
SIMATIC PDM/
PLC
Symbol
Symbol
Description
-
Data exchanged
-
No data exchanged
-
Write protection disabled
EDIT
-
● 'EDIT' is permanently enabled in the parameter view. You can read the parameter.
● 'EDIT' flashes in the edit view. You can change the parameter.
L
Device is write-protected by a jumper.
LL
Button lock of device is enabled
LP
Parameters and device functions are write-protected with a user PIN.
SIL
-
Functional Safety is enabled
Co
-
The output current is constant (e.g. for loop test).
Diagnostics and troubleshooting
12.2 Diagnostic messages
SITRANS P320/P420 (mA/HART)
Operating Instructions, 06/2018, A5E44852162-AA
189
Содержание SITRANS P320
Страница 10: ...Table of contents SITRANS P320 P420 mA HART 10 Operating Instructions 06 2018 A5E44852162 AA ...
Страница 18: ...Introduction 2 7 Notes on warranty SITRANS P320 P420 mA HART 18 Operating Instructions 06 2018 A5E44852162 AA ...
Страница 174: ...Functional Safety 10 7 Repair and service SITRANS P320 P420 mA HART 174 Operating Instructions 06 2018 A5E44852162 AA ...
Страница 260: ...Index SITRANS P320 P420 mA HART 260 Operating Instructions 06 2018 A5E44852162 AA ...