
4. To complete validation of the safety-related parameters, confirm with YES.
5. To validate the fail-safe behavior, start the function test with "START".
When you select "SKIP", you skip the function test and enable Functional Safety directly
without validation of the fail-safe behavior.
Validate fail-safe behavior
1. Check the correct execution of the fail-safe behavior in which the device is used.
2. In the parameter view, select the "Functional Safety" parameter [29].
3. To continue with the wizard, enter the user PIN if needed.
4. Select "START".
5. Use the button to confirm.
6. When you have successfully validated the fail-safe behavior, restart the wizard and select
"PASSD".
The message "SAFETY MODE ON" (Functional Safety enabled) appears.
Functional Safety
10.2 Enabling Functional Safety
SITRANS P320/P420 (mA/HART)
162
Operating Instructions, 06/2018, A5E44852162-AA
Содержание SITRANS P320
Страница 10: ...Table of contents SITRANS P320 P420 mA HART 10 Operating Instructions 06 2018 A5E44852162 AA ...
Страница 18: ...Introduction 2 7 Notes on warranty SITRANS P320 P420 mA HART 18 Operating Instructions 06 2018 A5E44852162 AA ...
Страница 174: ...Functional Safety 10 7 Repair and service SITRANS P320 P420 mA HART 174 Operating Instructions 06 2018 A5E44852162 AA ...
Страница 260: ...Index SITRANS P320 P420 mA HART 260 Operating Instructions 06 2018 A5E44852162 AA ...