Example
For the volume measurement, you set the following values, for example:
Damping value:
2.0 s
Lower range value:
0.0 mbar
Upper range value:
500.0 mbar
Application:
Cylinder vessel (CYLIN)
Unit:
m
3
Lower scaling point:
0.0 m
3
Upper scaling point:
10.0 m
3
9.2.4.5
Set application
Procedure
1. Navigate to the parameter view.
Navigating in the views (Page 71)
2. Select the "Application" parameter [05].
3. Select the parameter value.
Result
You have set the application of your device.
9.2.5
Application point [06]
Sets the application point from which scaling occurs according to the square root. Before the
application point, the scaling occurs in a linear relationship with the differential pressure.
This parameter is only visible when you have selected "Linear, square root" (VSLIN or MSLIN)
or "Hold at 0, square root" (VSOFF or MSOFF) using the "Application" parameter.
Setting range:
5 to 15%
Factory setting:
10%
See also
Volume and mass flow measurements (Page 111)
Parameter assignment
9.2 Parameter assignment over device with display
SITRANS P320/P420 (mA/HART)
Operating Instructions, 06/2018, A5E44852162-AA
115
Содержание SITRANS P320
Страница 10: ...Table of contents SITRANS P320 P420 mA HART 10 Operating Instructions 06 2018 A5E44852162 AA ...
Страница 18: ...Introduction 2 7 Notes on warranty SITRANS P320 P420 mA HART 18 Operating Instructions 06 2018 A5E44852162 AA ...
Страница 174: ...Functional Safety 10 7 Repair and service SITRANS P320 P420 mA HART 174 Operating Instructions 06 2018 A5E44852162 AA ...
Страница 260: ...Index SITRANS P320 P420 mA HART 260 Operating Instructions 06 2018 A5E44852162 AA ...