9.2.33.3
Restore ordered configuration
With this function you return your device to its delivery state.
● The ordered configuration of the following parameters is restored:
– Pressure units
– Quick start
– Pressure reference
– Long tag (TAG)
– Short tag (TAG)
– Lower range value
– Upper range value
– Lower limit of the measuring range
– Upper limit of the measuring range
– Damping value
– Application and related values (e.g.: vessel shapes and application points)
– Fault current selection
– Lower fault current
– Upper fault current
– Lower saturation limit
– Upper saturation limit
– Custom units
● The parameters that you have not configured via the order are reset to the factory settings.
9.2.33.4
Restore factory settings
With this function you return your device to its factory setting.
The following settings are reset to the factory setting among other things:
● Sensor calibration
● DAC trim
● The defaults that you have configured in your order.
These defaults can then deviate from the ordered configuration. To restore the ordered
configuration, use the "Restore ordered configuration (Page 141)" parameter.
Parameter assignment
9.2 Parameter assignment over device with display
SITRANS P320/P420 (mA/HART)
Operating Instructions, 06/2018, A5E44852162-AA
141
Содержание SITRANS P320
Страница 10: ...Table of contents SITRANS P320 P420 mA HART 10 Operating Instructions 06 2018 A5E44852162 AA ...
Страница 18: ...Introduction 2 7 Notes on warranty SITRANS P320 P420 mA HART 18 Operating Instructions 06 2018 A5E44852162 AA ...
Страница 174: ...Functional Safety 10 7 Repair and service SITRANS P320 P420 mA HART 174 Operating Instructions 06 2018 A5E44852162 AA ...
Страница 260: ...Index SITRANS P320 P420 mA HART 260 Operating Instructions 06 2018 A5E44852162 AA ...