3.8 mA
22.8 mA
20 mA
20.5 mA
4 mA
3.55 mA
①
Normal operation
②
Lower fault current (factory setting)
③
Lower saturation limit (factory setting)
④
Upper saturation limit (factory setting)
⑤
Upper fault current (factory setting)
9.2.10
Upper fault current [12]
Adjusts the magnitude of the upper fault current
⑤
.
Setting range:
Between upper saturation limit
④
und 22.8 mA
Factory setting:
22.8 mA, or as specified in order
3.8 mA
22.8 mA
20 mA
20.5 mA
4 mA
3.55 mA
①
Normal operation
②
Lower fault current (factory setting)
③
Lower saturation limit (factory setting)
④
Upper saturation limit (factory setting)
⑤
Upper fault current (factory setting)
9.2.11
Lower saturation limit [13]
Sets the lower threshold for the lower saturation limit
③
.
The loop current cannot drop below the set threshold.
Setting range:
Between lower fault current
②
and 4 mA
Factory setting:
3.8 mA, or as specified in order
Parameter assignment
9.2 Parameter assignment over device with display
SITRANS P320/P420 (mA/HART)
Operating Instructions, 06/2018, A5E44852162-AA
121
Содержание SITRANS P320
Страница 10: ...Table of contents SITRANS P320 P420 mA HART 10 Operating Instructions 06 2018 A5E44852162 AA ...
Страница 18: ...Introduction 2 7 Notes on warranty SITRANS P320 P420 mA HART 18 Operating Instructions 06 2018 A5E44852162 AA ...
Страница 174: ...Functional Safety 10 7 Repair and service SITRANS P320 P420 mA HART 174 Operating Instructions 06 2018 A5E44852162 AA ...
Страница 260: ...Index SITRANS P320 P420 mA HART 260 Operating Instructions 06 2018 A5E44852162 AA ...