87
PBD-51041059
SITRANS LG260 - Operating Instructions
44284-EN-171021
ScadaPack
Wiring plan
+
+
power suppl
y
MODBUS
D0
D1
IS GND
US
B
1
3
2
13
45
5
2
1
3
4
9
6
7
8
2o
ff
on
(
)
( )
(-)
(-)
+8
+30 Vdc
to
GND
COM Part 3 (C3)
RS485
TXD-
TXD+
GND
Fig. 49: Connection of SITRANS LG260 to RTU ScadaPack
1 SITRANS LG260
2 RTU ScadaPack
3 Voltage supply
Parameter
Parameter
Value
Baud Rate
9600
Floating Point Format Code
0
RTU Data Type
Floating Point
Input Register Base Number
30001
The basic number of the input registers is always added to the input register address of SITRANS
LG260.
Address 31303 must hence be entered as register address for 1302 for RTU ScadaPack.