84
PBD-51041059
SITRANS LG260 - Operating Instructions
44284-EN-171021
ABB Total Flow
Wiring plan
+
+
power suppl
y
MODBUS
D0
D1
IS GND
US
B
1
2
13
45
2o
ff
on
(
)
( )
(-)
(-)
8
1
2
6
7
Bus +
Bus -
GND
VBAT
Fig. 46: Connection of SITRANS LG260 to RTU ABB Total Flow
1 SITRANS LG260
2 RTU ABB Total Flow
Parameter
Parameter
Value
Baud Rate
9600
Floating Point Format Code
0
RTU Data Type
16 Bit Modicon
Input Register Base Number
1
The basic number of the input registers is always added to the input register address of SITRANS
LG260.
Address 1303 must hence be entered as register address for 1302 for RTU ABB Total Flow.