38
PBD-51041059
SITRANS LG260 - Operating Instructions
44284-EN-171021
Menu
Menu item
Default value
Setup
Current output, output variable
First HART variable (PV)
Lin. percent - Level
Current output - Output characteristics
0 … 100 % correspond to
4 … 20 mA
Current output - Reaction in case of fault
≤ 3.6 mA
Current output - Min.
3.8 mA
Current output - Max.
20.5 mA
Current output 2 - Output variable
Second HART variable (SV)
Distance - Level
Current output 2 - Output characteristics
0 … 100 % correspond to
4 … 20 mA
Current output 2 - Reaction in case of fault
≤ 3.6 mA
Current output - Min.
3.8 mA
Current output - Max.
20.5 mA
Setup
Third HART variable (TV)
Measurement certainty, level
Fourth HART variable (QV)
Electronics temperature
Menu - Display
Menu
Menu item
Default value
Display
Language
Selected language
Displayed value 1
Filling height Level
Displayed value 2
Electronics temperature
Display format 1
Automatically
Display format 2
Automatically
Backlight
Switched on
Menu - Additional adjustments
Menu
Menu item
Default value
Additional adjustments PIN
0000
Date
Actual date
Time
Actual time
Time - Format
24 hours
Probe type
Device-specific
The instrument settings are copied with this function. The following
functions are available:
•
Read from sensor: Read data from sensor and save in the display
and adjustment module
•
Write to sensor: Save data from the display and adjustment mod-
ule back into the sensor
Additional settings - Copy
instrument settings