SITRANS LG260 - Operating Instructions
44284-EN-171021
Thermo Electron Autopilot
Wiring plan
+
+
power suppl
y
MODBUS
D0
D1
IS GND
US
B
1
2
3
13
45
2o
ff
on
(
)
( )
(-)
(-)
+8
+30 Vdc
to
GND
2
1
Rx -
Rx+
Fig. 47: Connection of SITRANS LG260 to RTU Thermo Electron Autopilot
1 SITRANS LG260
2 RTU Thermo Electron Autopilot
3 Voltage supply
Parameter
Parameter
Value
Baud Rate
9600
Floating Point Format Code
0
RTU Data Type
IEE Fit 2R
Input Register Base Number
0
The basic number of the input registers is always added to the input register address of SITRANS
LG260.
For that reason, address 1300 must be entered as register address for 1300 for the RTU Thermo
Electron Autopilot.