67
PBD-51041059
SITRANS LG260 - Operating Instructions
44284-EN-171021
L
0
-2mm
(-0.079")
2mm
(0.079")
15mm
(0.591")
-10mm
(-0.394")
0,3 m
(11.811")
0,08 m
(3.15")
0,02 m
(0.787")
1
Fig. 40: Deviation SITRANS LG260 in rod version
1 Dead band (no measurement possible in this area)
L Probe length
0
2mm
(0.079")
-2mm
(-0.079")
15mm
(0.591")
10mm
(0.394")
0,08 m
(3.15")
0,3 m
(11.811")
0,1 m
(3.94")
L
1
Fig. 41: Deviation SITRANS LG260 in cable version in water
1 Dead band (no measurement possible in this area)
L Probe length
Repeatability
≤ ±1 mm
Variables influencing measurement accuracy
Temperature drift - Digital output
±3 mm/10 K relating to the max. measuring range or
max. 10 mm (0.394 in)
Additional deviation through electromag-
netic interference acc. to EN 61326
< ±10 mm (< ±0.394 in)
Influence of the superimposed gas and pressure on measurement accuracy
The propagation speed of the radar impulses in gas or vapour above the medium is reduced by
high pressure. This effect depends on the superimposed gas or vapours.