05/2016 - A5E36751269-AA
M
Configuration
Incons. Converter Calib.
Faulty calibration data in the
converter module.
Contact the manufacturer.
Incons. Sensor Calibration
Faulty calibration data in the
sensor module
SIL Verification Required
SIL mode is requested. A
verification (maintenance
mode 2) has to be performed
by the operator.
Verify the parameters for
the SIL mode according to
the instructions of the safety
manual and confirm the
correctness with the SIL
jumper.
S
Config: Totalizer
Flow Totalizer Overflow
The actual value of the flow
counter exceeds its preset
value.
Check the setting of the flow
counter or reset the counter.
Energy Totalizer Overflow
The actual value of the
energy counter exceeds its
preset value.
The actual value of the
energy counter exceeds its
preset value.
M
Sensor Information
Meas. Signal Too Strong
The vortex amplitude is
saturated. The
measurement can be
continued, but the signal
might be disturbed.
Check the process
conditions and the
installation situation.
Eliminate external
disturbances. If the
message recurs, contact the
manufacturer.
Flow Meas. Signal Disturb.
The vortex signal is
disturbed.
Failed Piezo Test
The continuous self test of
the sensor electronic failed.
Perform a hard reset. If the
message recurs, contact the
manufacturer.
Failed Sensor Input Test
Failed Sensor MCU Test
Status
type
Event group
Single event
Description
Actions to eliminate the
event