Parameter lists
A.2 Output
SITRANS FUS080 transmitter
Operating Instructions, 07/2012, A5E03059912-02
71
A.2
Output
Table A- 2
Output parameters
Modbus
Address
Parameter
Default
value
Value range
Access
level
Description
43023
100 Actual date and time
Product
dependent
R/W
Actual date and time (day-month-
year and hours:minutes:seconds)
43006
101 Totalizer 1
0
-2000000001
...
+2000000001
Read
Volume for totalization register 1
43010
102 Totalizer 2
0
-2000000001
...
+2000000001
Read
Volume for totalization register 2
43014
103 Customer totalizer 3
0
Read
Customer totalizer 3 based on
totalizer 1 set up
19
104 Reset customer totalizer 3 No
No, Yes
R/W
Reset of customer totalizer
40732
105 Customer totalizer 3 reset
date
last reset
date
dd-mm-yyyy,
hh:mm:ss
Date and time when customer
totalizer has been reset
43001
106 Flow rate
Read
Actual flow value
43136
107 Relative flow rate
0
Read
Actual flow value in relation to Qmax
43035
108 Actual velocity for path 1
0
Read
The actual flow velocity for path 1 in
m/s (SI-unit)
43046
109 Actual velocity for path 2
0
The actual flow velocity for path 2 in
m/s (SI-unit).
Valid for 2-path solutions only
43026
110 Path 1 gain step
15
1 to 15
Read
Amplifier setting when measuring
path 1
43037
111 Path 2 gain step
15
1 to 15
Read
Amplifier setting when measuring
path 2.
Valid for 2-path solutions only
Pulse A B
40817
430 Output A enable
Yes
No, Yes
R/W
Select 'Yes' to enable output A
40818
431 Pulse A function
Forward
Forward,
Reverse,
Forward net,
Reverse net
R/W
Pulse output calculation on pure
forward flow or pure reverse flow -
or net flow for forward and reverse
pulse flow.
Valid if pulse output A is enabled
40819
432 Amount per pulse A
1.000000
(m
3
)
0.000001 ...
1000000000
R/W
Volume per pulse and selected unit
Valid if pulse output A is enabled.
40821
433 Pulse width for pulse A
5 ms
5, 10, 20, 50,
100, 200, 500
ms
R/W
Pulse length when the pulse is
active.
Valid if pulse output A is enabled
40822
440 Output B enable
Yes
No, Yes
R/W
Select 'Yes' to enable output B
40823
441 Pulse B function
Alarm
Pulse, Alarm,
Call up
R/W
Configuration of output B as pulse -
alarm or call up function.
Valid if pulse output B is enabled
Содержание SITRANS F US SONOKIT
Страница 2: ......
Страница 8: ...Table of contents SITRANS FUS080 transmitter 6 Operating Instructions 07 2012 A5E03059912 02 ...
Страница 16: ...Safety notes 2 4 Certificates SITRANS FUS080 transmitter 14 Operating Instructions 07 2012 A5E03059912 02 ...
Страница 46: ......
Страница 50: ...Functions 7 4 Hardware key SITRANS FUS080 transmitter 48 Operating Instructions 07 2012 A5E03059912 02 ...
Страница 70: ...Qualification certificate SITRANS FUS080 transmitter 68 Operating Instructions 07 2012 A5E03059912 02 ...