4.1.4
Split mode
The split mode divides the measuring range
into two domains:
• Domain 1 from 0 to
’Split value’
• Domain 2 from ’Split
value’ to ’URV’
(upper range value, menu3.1.2)
At digital outputs 1 or 2, it is possible to
indicate whether the current measured val‐
ue is within domain 1.
To do this, the function ’Split value active’
must be set (menu 4.2.1 and 4.3.1)
Inactive
• Inactive
• Active
Split value
End value of domain 1 (only when ’Split
mode = active’)
URV (menu
3.1.2)
Depends on the nominal
width (corresponding to
0.25 ... 12 m/s, <URV)
4.1
PROFIBUS
3
PROFIBUS communication
4.1.1
Bus Address
PROFIBUS address
126
1 to 126
4.1.2
Ident-Nr.
Selection of appropriate device database
file (GSD)
Manufact.spec.
• Profile spec.
• Manufact.spec.
4.2
Digit.Output
1
Frequency or pulse signal for flow or alarm
signal
4.2.1
Function
Assignment of a function to digital output 1
’Split value active’: the active output indi‐
cates a current flow value in the 0 to ’Split
value’ range (not effective for PROFIBUS).
Pulse
• Pulse, Frequency,
• Alarm, Flow direction
forw.
• Flow min, Flow max,
Flow min/max,
• Total. forw. max,
• Total. rev. min,
• Total. net max,
• Total. net min
• Split value active,
• No function
4.2.2
Signal Type
Definition of signal logic for active event
Passive-pos.
• Active-pos., 1, 2
• Active-neg., 1, 2
• Passive-pos.
• Passive-neg.
4.2.3
Pulse Rate
Engr. Unit
Pulse Rate
Number of pulses per unit of quantity (only
effective with "Pulse" function)
Engineering unit of quantity to which the
number of pulses refers
Number of pulses per unit of quantity
DN1...12: Imp/l
>DN12: Imp/m
3
Depending on
the nominal
width 10Imp/l...
1Imp/m
3
• pulses/l, m
3
, Ml, ft
3
, Gal,
MGal, ImpGal, Mimp•
Gal, kg, t, lb,
• 0.01 ... 9999 pulses/unit
4.2.4
Pulse Width
(only with "Pulse" function)
+0.1 ms
0.1 ... 2000 ms
Parameters
TRANSMAG 2 with MAG 911/E
Operating Instructions, 03/2021, A5E00102775-AC
99
Содержание SITRANS F TRANSMAG 2
Страница 6: ...Table of contents TRANSMAG 2 with MAG 911 E 6 Operating Instructions 03 2021 A5E00102775 AC ...
Страница 10: ...Introduction 1 8 Notes on warranty TRANSMAG 2 with MAG 911 E 10 Operating Instructions 03 2021 A5E00102775 AC ...
Страница 52: ...Operating 7 2 SIMATIC PDM TRANSMAG 2 with MAG 911 E 52 Operating Instructions 03 2021 A5E00102775 AC ...
Страница 84: ...Troubleshooting 10 3 Error messages TRANSMAG 2 with MAG 911 E 84 Operating Instructions 03 2021 A5E00102775 AC ...
Страница 92: ...Dimension drawings TRANSMAG 2 with MAG 911 E 92 Operating Instructions 03 2021 A5E00102775 AC ...
Страница 104: ...Parameters TRANSMAG 2 with MAG 911 E 104 Operating Instructions 03 2021 A5E00102775 AC ...
Страница 126: ...Index TRANSMAG 2 with MAG 911 E 126 Operating Instructions 03 2021 A5E00102775 AC ...