IO-Link 3SU14
12.3 Electronic modules for IO-Link
SIRIUS ACT 3SU1 pushbuttons and signaling devices
System Manual, 08/2018, A5E03457306020A/RS-AK/010
351
12.3.3.1
"Input delay” parameter
"Input delay
"
parameter
A delay time must be set at the input as a filter. Signal changes are ignored if they are
shorter than the parameterized values. The input values are delayed by the time set for the
filter. Values of between 3 and 255 ms can be set as the input delay.
Settings
Description
Default setting
3
Input delay: Minimum value
3 ms
255
Input delay: Maximum value
—
Increment: 1 ms
12.3.3.2
"Inverting input” parameter
"Inverting input" parameter
Each input can be parameterized as a normal or an inverting input.
Settings
Description
Default setting
0
Inverting input: disabled
disabled
1
Inverting input: enabled
—
12.3.3.3
"Switching input” parameter
"Switching input” parameter
Target value with which the actual switching cycle number is compared. The number of
switching cycles can be set to between 0 and 4 294 967 295 (0xFFFFFFF [hex]).
Settings
Description
Default setting
0
Number of switching cycles: Minimum value
0
4294967295
Number of switching cycles: Maximum value
—
Increment: 1