43-TV-25-35 GLO Iss.4 Dec 06 UK
83
A5E01001767-04
Power up
•
Period -
Only available when Interval is selected as a Sub Type. Set the time interval
for how often this event should occur, eg. every hour would be 1h:00m:00s
•
Alignment -
Only available when Interval is selected as a Sub Type. Select and enter a
value from the list to align the scheduled event at specific intervals.
For certain applications it maybe desirable for a relatively fast schedule interval event,
for example every 10 minutes, to be aligned with a particular time. For example on the
hour.
When the alignment function is not used, the schedule interval starts immediately on
committing the configuration. When the alignment function is used, the schedule inter-
val starts when the first interval event coincides with a subsequent interval that lines up
with the desired alignment ie. Top of the hour.
shows if a 10 minutes schedule is required to align with a whole hour, and the
configuration is committed at 17 minutes past, the recorder will wait until 20 past before
starting the schedule interval. As starting at 20 past with 10 minute increments will ensure
alignment with a whole hour.
•
Count -
Only available when Interval, Specific Days or Month End are selected as a
Sub Type. This is how often you want this to occur. The recorder will carry on with this
schedule for the amount entered in the count. Eg. If 24 is entered into the count the
scheduled event will occur at the specified time for 24 hours. A count of zero will carry
on indefinately.
•
Days of the Week -
Only available when Specific Days is selected as a Sub Type.
Select the days of the week when this scheduled event is to occur.
•
Time of Day -
Only available when Specific Days is selected as a Sub Type. Select the
Time Of Day when this scheduled event is to occur.
User Counters
User Counters are quite simply counters that are set up by the user. User Counters can be
used as a Cause to trigger an Event Effect. The User Counter information must be setup in
the before it can be used as a part of the event system.
.
For a User Counter to be used as a Cause, a User Counter must already be set up and be
counting something. eg. a User Counter as an Effect of another Event.
Time
1.00
1.10 1.20 1.30 1.40 1.50
2.00
2.10 2.20 2.30 2.40 2.50
3.00
non aligned
aligned to
the hour
Example of a schedule interval event
started at 17 minutes past the hour
Figure 4.9 Interval alignment
Содержание SIREC D200
Страница 2: ......
Страница 176: ...170 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 Firmware Credit System ...
Страница 213: ...43 TV 25 35 GLO Iss 4 Dec 06 UK 207 A5E01001767 04 SIREC D400 Recorder 14 15 32 46 50 30 31 35 36 28 55 ...
Страница 214: ...208 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 52 11 23 33 39 5 6 RS485 USB host Ethernet 1 2 3 4 ...
Страница 218: ...212 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 SIREC D200 Recorder 16 5 3 1 4 2 24 49 9 45 19 6 49 ...
Страница 222: ...216 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 ...
Страница 238: ...232 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 ...
Страница 258: ...252 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 ...
Страница 270: ...264 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 ...
Страница 274: ...268 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 Modbus Function Codes ...
Страница 284: ...278 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 ...
Страница 285: ......