43-TV-25-35 GLO Iss.4 Dec 06 UK
135
A5E01001767-04
Power up
**any increase is measured from the level when the recorder is first powered up.
Analogue Out Status
(Main Menu > Status > Diagnostics > Hardware > Analogue Out))
Not available for the
SIREC D200
.
•
Channel
- Displays the Slot position, eg. B, E or F, the Analogue Output number and
the system channel position. This will show a tick if this channel is enabled.
•
TX Pen
- Displays which pen is transmitting the signal
•
Range
- Displays the Output range set. A tick here will indicate this is over-range.
•
Output
- Displays the current Analogue Output reading for this channel.
Go
Back
to return to the previous screen or select
to print the screen.
Alarm/Digital IO Status
(Main Menu > Status > Diagnostics > Digital IO)
•
Channel
- Displays the Slot position, eg. G, H or I, the Digital IO number and the system
channel position. This will show a tick if this channel is enabled. Fixed refers to the com-
mon relay output on the power board (24V relay)
•
Input/Output/Pulse
- Displays what activity is on this channel, Input, Output or Pulse
Input.
•
Alarm
- Displays the Pen number and the Alarm number that activates the digital output
when the alarm is active. The Alarm has to be set to Relay out.
•
Status -
Displays the current state of the digital input on this channel or pulsed if Pulse
Out is selected. The relay is displayed as open or closed.
•
Counters
- Displays the counter number when active.
•
Duration
- Displays the Output Pulse duration set.
Go
Back
to return to the previous screen or select
to print the screen.
Failing
Thermocouple Failing (difference measurement: 100
Ω
to 200
Ω
increase**)
Failing
Thermocouple Failing (absolute measurement: over 230
Ω
increase**)
Almost Failed
Thermocouple Almost Failed (difference measurement: over 200
Ω
, not failed)
Almost Failed
Thermocouple Almost Failed (absolute measurement: 330
Ω
to 2k
Ω
)
Open Circuit
Thermocouple Failed, No data on passive channel,
Thermocouple Failed, but no error on passive thermocouple channel
Thermocouple Failed, also failed status on passive channel
Short Circuit
Possible thermocouple wiring short circuit detected (significant reduction in
Ω
)
Table 4.11 : Thermocouple Active Burnout Status
Label
Descriptions
Содержание SIREC D200
Страница 2: ......
Страница 176: ...170 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 Firmware Credit System ...
Страница 213: ...43 TV 25 35 GLO Iss 4 Dec 06 UK 207 A5E01001767 04 SIREC D400 Recorder 14 15 32 46 50 30 31 35 36 28 55 ...
Страница 214: ...208 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 52 11 23 33 39 5 6 RS485 USB host Ethernet 1 2 3 4 ...
Страница 218: ...212 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 SIREC D200 Recorder 16 5 3 1 4 2 24 49 9 45 19 6 49 ...
Страница 222: ...216 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 ...
Страница 238: ...232 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 ...
Страница 258: ...252 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 ...
Страница 270: ...264 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 ...
Страница 274: ...268 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 Modbus Function Codes ...
Страница 284: ...278 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 ...
Страница 285: ......