1304 DIREC. Z1
Zone 1: Direction
FORWARDS
[ ] Forwards
REVERSE
[ ] Reverse
NON-DIRECTIONAL [ ] Non-directional
1305 T1 1PHASE
Zone 1: Delay for single phase faults T1 1PH
min. 0.00
s
max. 32.00/Ñ
©©©©
1306 T1 >1PHASE
Zone 1: Delay for multi-phase faults T1
min. 0.00
s
max. 32.00/Ñ
©©©©
1311 R2
Zone 2: Resistance (phase-phase) R2
min. 0.05
Ï
max. 65.00
©©©©
1312 X2
Zone 2: Reactance (reach) X2
min. 0.05
Ï
max. 130.00
©©©©
1313 R2E
Zone 2: Resistance (phase-earth) R2E
min. 0.05
Ï
max. 130.00
©©©©
1314 DIREC. Z2
Zone 2: Direction
FORWARDS
[ ] Forwards
REVERSE
[ ] Reverse
NON-DIRECTIONAL [ ] Non-directional
1315 T2 1PHASE
Zone 2: Delay for single phase faults T2 1PH
min. 0.00
s
max. 32.00/Ñ
©©©©
1316 T2 >1PHASE
Zone 2: Delay for multi-phase faults T2
min. 0.00
s
max. 32.00/Ñ
©©©©
1317 TRIP 1P Z2
Single pole trip for faults in Z2
NO
[ ] no
YES
[ ] yes
1321 R3
Zone 3: Resistance (phase-phase) R3
min. 0.05
Ï
max. 65.00
©©©©
1322 X3
Zone 3: Reactance (reach) X3
min. 0.05
Ï
max. 130.00
©©©©
1323 R3E
Zone 3: Resistance (phase-earth) R3E
min. 0.05
Ï
max. 130.00
©©©©
1324 DIREC. Z3
Zone 3: Direction
FORWARDS
[ ] Forwards
REVERSE
[ ] Reverse
NON-DIRECTIONAL [ ] Non-directional
1325 T3
Zone 3: Delay for all faults T3
min. 0.00
s
max. 32.00/Ñ
©©©©