2900 MEAS.VALUE SUPERVISION
2901 SYM.Uthres
Symmetry threshold for voltage monitoring
min. 10
V
max. 100
©©©©
2902 SYM.Fact.U
Symmetry factor for voltage monitoring
min. 0.58
max. 0.95
©©©©
2903 SYM.Ithres
Symmetry threshold for current monitoring
min. 0.10
I/In
max. 1.00
©©©©
2904 SYM.Fact.I
Symmetry factor for current monitoring
min. 0.10
max. 0.95
©©©©
2905 SUM.Ithres
Summation threshold for current monitoring
min. 0.10
I/In
max. 2.00
©©©©
2906 SUM.Fact.I
Factor for current summation monitoring
min. 0.00
max. 0.95
©©©©
2907 UMEAS U<
Threshold for voltage failure monitor
min. 10
V
max. 125
©©©©
2908 UMEAS I>
Minimum current for voltage failure monitor
min. 0.06
I/In
max. 1.00
©©©©
2910 FUSE-FAIL
Fuse failure monitoring (FFM)
ON
[ ] on
OFF
[ ] off
2911 FFM 3*Uo>
Displacement voltage level for FFM
min. 10
V
max. 100
©©©©
2912 FFM Ie<
Earth current for fuse failure monitoring
min. 0.10
I/In
max. 1.00
©©©©
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
3000 EARTHFAULT NON-EARTHED NET
3001 EARTHFAULT
Sensitive earth fault det. in non-earthed net
ALARM ONLY
[ ] Alarm only
ON
[ ] on
OFF
[ ] off
3002 Ue>
Displacement voltage level Ue>
min. 10
V
max. 100
©©©©
3003 Uph<
Phase-earth voltage of faulted phase Uph<
min. 10
V
max. 100
©©©©