7410 T-MAX
Maximum time period of a fault recording
min. 0.30
s
max. 5.00
©©©©
7411 T-PRE
Pre-trigger time for fault recording
min. 0.05
s
max. 0.50
©©©©
7412 T-POST
Post-fault time for fault recording
min. 0.05
s
max. 0.50
©©©©
7431 T-BINARY IN
Storage time by initiation via binary input
min. 0.10
s
max. 5.00/Ñ
©©©©
7432 T-KEYBOARD
Storage time by initiation via keyboard
min. 0.10
s
max. 5.00
©©©©
7490 SYS LENGTH
Length of fault record (former LSA)
660 VALUES FIX
[ ] 660 values fix
<=3000 VAL. VAR [ ] <=3000 val. var
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
7800 SCOPE OF FUNCTIONS
7812 DIST. PROT.
Distance protection
EXIST
[ ] Existent
NON-EXIST
[ ] Non-existent
7813 DIST.F.DET.
Distance protection: Fault detection program
OVERCURRENT
[ ] Overcurrent FD.
IMPEDANCE ZONE
[ ] Impedance zone FD.
U/I FAULT DET.
[ ] U/I fault detection
7820 POWER SWING
Power swing detection
NON-EXIST
[ ] Non-existent
EXIST
[ ] Existent
7821 TELEPROTEC.
Teleprotection for distance protection
NON-EXIST
[ ] Non-existent
UNDERREACH
[ ] Underreach
OVERREACH
[ ] Overreach
7823 USER LOGIC
User definable logic functions
NON-EXIST
[ ] Non-existent
EXIST
[ ] Existent
7826 EMERG. O/C
Emergency overcurrent time protection
EXIST
[ ] Existent
NON-EXIST
[ ] Non-existent
7827 THERMAL OL
Thermal overload protection
NON-EXIST
[ ] Non-existent
EXIST
[ ] Existent
7830 ISOL. E/F
Earth fault detection for isol./comp. networks
NON-EXIST
[ ] Non-existent
EXIST
[ ] Existent