$SSHQGL[
6$
9
&*&
¿©©©©§©©©©©©©©©©©©©§©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©§©©§©©§©§©©©¤
FNo.Abbreviation Meaning
OpFtEIOT
¨©©©©ª©©©©©©©©©©©©©ª©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©ª©©ª©©ª©ª©©©
3703Loop L3-E f Dist.: Loop L3E selected forward
CG OT
3704Loop L1-2 f Dist.: Loop L12 selected forward
CG OT
3705Loop L2-3 f Dist.: Loop L23 selected forward
CG OT
3706Loop L3-1 f Dist.: Loop L31 selected forward
CG OT
3707Loop L1-E r Dist.: Loop L1E selected reverse
CG OT
3708Loop L2-E r Dist.: Loop L2E selected reverse
CG OT
3709Loop L3-E r Dist.: Loop L3E selected reverse
CG OT
3710Loop L1-2 r Dist.: Loop L12 selected reverse
CG OT
3711Loop L2-3 r Dist.: Loop L23 selected reverse
CG OT
3712Loop L3-1 r Dist.: Loop L31 selected reverse
CG OT
3719Dist. For.DirDist.: Fault det. in forward direction OT
3720Dist. Rev.DirDist.: Fault det. in reverse direction OT
3771Dist. T1
Dist.: Time T1 ( Zone Z1 ) expired
OT
3774Dist. T2
Dist.: Time T2 ( Zone Z2 ) expired
OT
3777Dist. T3
Dist.: Time T3 ( Zone Z3 ) expired
OT
3778Dist. T4
Dist.: Time T4 (direct. zone) expired OT
3779Dist. T5
Dist.: Time T5 (non-dir. zone) expired OT
3780Dist. T1B
Dist.: Time T1B ( Zone Z1B ) expired
OT
3783Dist. T1L
Dist.: Time T1L ( Zone Z1L ) expired
OT
3801Dis.Gen. TripDistance protection: General trip
OT
3802Dis.Trip 1pL1Dist.: Trip phase L1 1pole only
C OT
3803Dis.Trip 1pL2Dist.: Trip phase L2 1pole only
C OT
3804Dis.Trip 1pL3Dist.: Trip phase L3 1pole only
C OT
3805Dis.Trip 3p Dist.: Trip 3pole
C OT
3808Dis.Trip backDist.: Trip in back-up stage
OT
3811Dis.TripZ1/1pDist.: Trip 1pole in zone Z1/T1
OT
3812Dis.TripZ1/3pDist.: Trip 3pole in zone Z1/T1
OT
3813Dis.TripZ1B1pDist.: Trip 1pole in zone Z1B/T1B
OT
3814Dis.TripZ1B3pDist.: Trip 3pole in zone Z1B/T1B
OT
3815Dis.Trip Z1L Dist.: Trip for fault in zone Z1L/T1L OT
3816Dis.TripZ2/1pDist.: Trip 1pole in zone Z2/T2
OT
3817Dis.TripZ2/3pDist.: Trip 3pole in zone Z2/T2
OT
3818Dis.TripZ3/T3Dist.: Trip for fault in zone Z3/T3
OT
3819Dis.Trip FD->Dist.: Trip by fault detection, direct OT
3820Dis.Trip <-> Dist.: Trip by fault detec., non-direct OT
4004>Dis. Recept >Dist. teleprotection: Carrier receive C C IOT
4005>Dis.RecFail >Dist. teleprotection: Carrier faulty CG IOT
4011>Dis.POTT on >Dist.:Switch on teleprotection POTT
IOT
4012>Dis.POTT off>Dist.:Switch off teleprotection POTT IOT
4021>Dis.PUTT on >Dist.:Switch on teleprotection PUTT
IOT
4022>Dis.PUTT off>Dist.:Switch off teleprotection PUTT IOT
4051Dis.Tele.on Dist. teleprotection is switched on
OT
4052Dis.Tele.off Dist. teleprotection is switched off
CG OT
4054Dis. Recept Dist. teleprotection: Carrier reception OT
4055Dis. RecFail Dist. teleprotection: Carrier faulty
CG OT
4056Dis. Send
Dist. teleprotection: Carrier send
C OT
4067Dis.POTT EchoPOTT teleprotection: Carrier echo send C OT
4068Dis.TransBlo POTT teleprotection: Transient block
C OT
4164Power Swing Power swing detection
CG OT
4165P/S T-action Power swing action time running
OT
4166O/S Trip
Out-of-step trip 3pole
C C OT
4403>Ext.Trip blk>Block external trip function
CG IOT
4412>Ext.Trip L1 >External trip L1 via binary input
C IOT
4413>Ext.Trip L2 >External trip L2 via binary input
C IOT
4414>Ext.Trip L3 >External trip L3 via binary input
C IOT
4416>Ext.Trp.woAR>External 3pole trip without AR
CG IOT
4431Ext.Gen. TripExt. trip via binary input: Trip
OT
4432Ext.Trip 1pL1Ext. trip via binary input: 1pole L1
C OT
¥©©©©¦©©©©©©©©©©©©©¦©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©¦©©¦©©¦©¦©©©¾