Technical Data
4.1 General Device Data
SIPROTEC, 7RW80, Manual
C53000-G1140-C233-1, Release date 10.2010
184
4.1.9
Design
4.1.10
UL certification conditions
Case
7XP20
Dimensions
see dimensional drawings, Section 4.12
Variant
Case
Size
Weight
(mass)
7RW80**-*B
in surface mounting housing
1
/
6
8.8 lb or 4.5 kg
7RW80**-*E
in flush mounting housing
1
/
6
8.8 lb or 4 kg
International Protection Under IEC 60529
For surface mounting housing equipment
IP 50
For flush mounted housing equipment
Front IP 51
Rear IP 50
For human safety
IP 1x for terminal voltage block
Degree of pollution IEC 60255-27
2
Output Relays
24 VDC
5 A General Purpose
48 VDC
0.8 A General Purpose
240 VDC
0.1 A General Purpose
240 VAC
5 A General Purpose
120 VAC
1/3 hp
250 VAC
1/2 hp
B300, R300
Voltage Inputs
Input voltage range
300 V
Battery
Servicing of the circuitry involving the batteries and replacement of the lithium bat-
teries shall be done by a trained technician.
Replace Battery with VARTA or Panasonic Cat. Nos. CR 1/2 AA or BR 1/2 AA only.
Use of another Battery may present a risk of fire or explosion. See manual for safety
instructions.
Caution: The battery used in this device may present a fire or chemical burn hazard
if mistreated. Do not recharge, disassemble, heat above 100 °C (212 °F) or inciner-
ate.
Dispose of used battery promptly. Keep away from children.
Climatic Stress Tests
Surrounding air temperature
tsurr: max. 70 °C (158 °F), normal opera-
tion
Design
Field Wires of Control Circuits shall be separated from other circuits with respect to
the end use requirements!
Type 1 if mounted into a door or front cover of an enclosure.