![Siemens SIPROTEC 7RW80 Скачать руководство пользователя страница 33](http://html.mh-extra.com/html/siemens/siprotec-7rw80/siprotec-7rw80_manual_382661033.webp)
Functions
2.1 General
SIPROTEC, 7RW80, Manual
C53000-G1140-C233-1, Release date 10.2010
33
2.1.3.3
Settings
Addresses which have an appended "A" can only be changed with DIGSI, under "Display Additional Settings".
Addr.
Parameter
Setting Options
Default Setting
Comments
202
Vnom PRIMARY
0.10 .. 800.00 kV
20.00 kV
Rated Primary Voltage
203
Vnom SECONDARY
34 .. 225 V
100 V
Rated Secondary Voltage (L-L)
206A
Vph / Vdelta
1.00 .. 3.00
1.73
Matching ratio Phase-VT To
Open-Delta-VT
209
PHASE SEQ.
A B C
A C B
A B C
Phase Sequence
210A
TMin TRIP CMD
0.01 .. 32.00 sec
0.15 sec
Minimum TRIP Command Dura-
tion
211A
TMax CLOSE CMD
0.01 .. 32.00 sec
1.00 sec
Maximum Close Command Dura-
tion
213
VT Connect. 3ph
Van, Vbn, Vcn
Vab, Vbc, VGnd
Vab, Vbc, VSyn
Vab, Vbc
Vph-g, VSyn
Vab, Vbc, Vx
Van, Vbn, Vcn
VT Connection, three-phase
214
Rated Frequency
50 Hz
60 Hz
50 Hz
Rated Frequency
220
Threshold BI 1
Thresh. BI 176V
Thresh. BI 88V
Thresh. BI 19V
Thresh. BI 176V
Threshold for Binary Input 1
221
Threshold BI 2
Thresh. BI 176V
Thresh. BI 88V
Thresh. BI 19V
Thresh. BI 176V
Threshold for Binary Input 2
222
Threshold BI 3
Thresh. BI 176V
Thresh. BI 88V
Thresh. BI 19V
Thresh. BI 176V
Threshold for Binary Input 3
223
Threshold BI 4
Thresh. BI 176V
Thresh. BI 88V
Thresh. BI 19V
Thresh. BI 176V
Threshold for Binary Input 4
224
Threshold BI 5
Thresh. BI 176V
Thresh. BI 88V
Thresh. BI 19V
Thresh. BI 176V
Threshold for Binary Input 5
225
Threshold BI 6
Thresh. BI 176V
Thresh. BI 88V
Thresh. BI 19V
Thresh. BI 176V
Threshold for Binary Input 6
226
Threshold BI 7
Thresh. BI 176V
Thresh. BI 88V
Thresh. BI 19V
Thresh. BI 176V
Threshold for Binary Input 7
232
VXnom PRIMARY
0.10 .. 800.00 kV
20.00 kV
Rated Primary Voltage X
233
VXnom SECONDARY
100 .. 225 V
100 V
Rated Secondary Voltage X