Functions
2.4 Load Restoration
SIPROTEC, 7RW80, Manual
C53000-G1140-C233-1, Release date 10.2010
65
5548
LR2 after 81-1
YES
NO
NO
Load restoration element 2 after
81-1
5549
LR2 after 81-2
YES
NO
NO
Load restoration element 2 after
81-2
5550
LR2 after 81-3
YES
NO
NO
Load restoration element 2 after
81-3
5551
LR2 after 81-4
YES
NO
NO
Load restoration element 2 after
81-4
5560
LR3
ON
OFF
OFF
Load restoration element 3
5561
LR3 Start
40.00 .. 60.00 Hz
47.50 Hz
Load restoration elem. 3 start fre-
quency
5562
LR3 Start
50.00 .. 70.00 Hz
57.50 Hz
Load restoration elem. 3 start fre-
quency
5563
LR3 Pickup
0.02 .. 2.00 Hz
0.04 Hz
Load restoration element 3
Pickup
5564
LR3 t pickup
0 .. 10800 sec
600 sec
Load restoration element 3
Pickup time
5565
LR3 Dropout
0.00 .. 2.00 Hz
0.02 Hz
Load restoration element 3
Dropout
5566
LR3 t dropout
0 .. 10800 sec
60 sec
Load restoration element 3
Dropout time
5567
LR3 t CB Close
0.01 .. 32.00 sec; 0
1.00 sec
Load restoration element 3 CB
Close time
5568
LR3 after 81-1
YES
NO
NO
Load restoration element 3 after
81-1
5569
LR3 after 81-2
YES
NO
NO
Load restoration element 3 after
81-2
5570
LR3 after 81-3
YES
NO
NO
Load restoration element 3 after
81-3
5571
LR3 after 81-4
YES
NO
NO
Load restoration element 3 after
81-4
5580
LR4
ON
OFF
OFF
Load restoration element 4
5581
LR4 Start
40.00 .. 60.00 Hz
47.50 Hz
Load restoration elem. 4 start fre-
quency
5582
LR4 Start
50.00 .. 70.00 Hz
57.50 Hz
Load restoration elem. 4 start fre-
quency
5583
LR4 Pickup
0.02 .. 2.00 Hz
0.04 Hz
Load restoration element 4
Pickup
5584
LR4 t pickup
0 .. 10800 sec
600 sec
Load restoration element 4
Pickup time
5585
LR4 Dropout
0.00 .. 2.00 Hz
0.02 Hz
Load restoration element 4
Dropout
5586
LR4 t dropout
0 .. 10800 sec
60 sec
Load restoration element 4
Dropout time
Addr.
Parameter
Setting Options
Default Setting
Comments