Integrated Power Supply
Auxiliary rated voltage V
H
(PS101)
Only for non-modular
devices
DC 24 V/DC 48 V
DC 60 V/DC 110 V/
DC 125 V
DC 110 V/ DC 125 V/
DC 220 V/DC 250 V
or
AC 100 V/AC 115 V/
AC 230 V, 50 Hz/60 Hz
Superimposed alternating
voltage, peak-to-peak,
IEC 60255-11,
IEC 61000-4-17
≤ 15 % of the DC auxiliary rated voltage (applies only to direct voltage)
Inrush current
≤ 18 A
Recommended external
protection
Miniature circuit breaker 6 A, characteristic C according to IEC 60898
Internal fuse
–
DC 24 V to DC 48 V
DC 60 V to DC 125 V
DC 24 V to DC 48 V
AC 100 V to AC 230 V
PS101
Only for non-modular
devices
4 A inert, AC 250 V,
DC 150 V,
UL recognized
SIBA type 179200 or
Schurter type SPT 5x20
2 A time-lag, AC 250 V, DC 300 V, UL recognized
SIBA type 179200 or Schurter type SPT 5x20
PS201, PS203, CB202
(to device version xA)
4 A inert, AC 250 V,
DC 150 V,
UL recognized
SIBA type 179200 or
Schurter type SPT 5x20
2 A time-lag, AC 250 V, DC 300 V, UL recognized
SIBA type 179200 or Schurter type SPT 5x20
PS201, PS203, PS204
(Device version xB and
higher)
4 A inert, AC 250 V,
DC 150 V,
UL recognized
SIBA type 179200 or
Schurter type SPT 5x20
3.15 A time-lag, AC 250 V, DC 300 V, UL recognized
SIBA type 179200 or Schurter type SPT 5x20
Power consumption (life relay active)
–
DC
AC 230 V/50 Hz
AC 115 V/50 Hz
1/3 module, non-modular
Without plug-in modules
7 W
16 VA
12.5 VA
1/3 base module, modular
Without plug-in modules
13 W
55 VA
40 VA
1/6 expansion module
3 W
6 VA
6 VA
1/6 plug-in module
assembly without plug-in
modules (modules CB202)
3.5 W
14 VA
7 VA
Plug-in module for base
module or plug-in module
assembly (for example,
communication module)
< 5 W
< 6 VA
< 6 VA
Technical Data
11.1 General Device Data
SIPROTEC 5, Low-Impedance Busbar Protection, Manual
903