Operate time for 2 ≤ I/I threshold value ≤ 20
5 % of the reference (calculated) value
+2 % current tolerance or 30 ms
Dropout time for 2 ≤ I/threshold value I ≤ 0.90
5 % of the reference (calculated) value
+2 % current tolerance or 30 ms
Influencing Variables for Threshold Values
Transient excess pickup in method of measurement =
fundamental component, for τ > 100 ms (with
complete unbalance)
< 5 %
Technical Data
11.16 Overcurrent Protection, Ground