Voltage-Balance Supervision
Setting Values
Release threshold
0.300 V to 170.000 V
Increments of 0.001 V
Threshold min/max
0.58 to 0.95
Increments of 0.01
Delay failure indication
0.00 s to 100.00 s
Increments of 0.01 s
Dropout Ratio
Overvoltage dropout ratio
Approx. 0.97
Undervoltage dropout ratio
Approx. 1.05
Times
Tripping time
Approx. 500 ms
Dropout time
Approx. 500 ms
11.24
Technical Data
11.24 Voltage-Balance Supervision
974
SIPROTEC 5, Low-Impedance Busbar Protection, Manual
C53000-G5040-C019-C, Edition 04.2021