Tolerances
Voltages
0.5 % of the setting value or 0.05 V
Time delays
1 % of the setting value or 10 ms
Undervoltage Protection with 3-Phase Voltage
Setting Values for Stage Type Definite Time-Undervoltage Protection
Measured value
Phase-to-phase
Phase-to-ground
Method of measurement
Fundamental component
RMS value
Current-flow criterion
On
Off
Threshold value
57
0.300 V to 175.000 V
Increments of 0.001 V
Time delay
0.00 s to 60.00 s
Increments of 0.01 s
Dropout ratio
1.01 to 1.20
Increments of 0.01
Setting Values for Stage Type Inverse Time-Undervoltage Protection
Measured value
Phase-to-phase
Phase-to-ground
Method of measurement
Fundamental component
RMS value
Current-flow criterion
On
Off
Threshold value
0.300 V to 175.000 V
Increments of 0.001 V
Pickup factor
0.80 to 1.00
Increments of 0.01
Characteristic constant k
0.00 to 300.00
Increments of 0.01
Characteristic constant α
0.010 to 5.000
Increments of 0.001
Characteristic constant c
0.000 to 5.000
Increments of 0.001
Time multiplier
0.05 to 15.00
Increments of 0.01
Additional time delay
0.00 s to 60.00 s
Increments of 0.01 s
Reset time
0.00 s to 60.00 s
Increments of 0.01 s
Operate Curve
T
op
=T
Inv
+ T
add
Where:
T
op
Operate delay
T
Inv
Inverse-time delay
T
add
Additional time delay (Parameter
Additional time delay
)
[fo_UVP3ph_1_3pol_inverse, 2, en_US]
11.19.6
57
If you have selected the Method of measurement = RMS value, do not set the threshold value to less than 10 V.
Technical Data
11.19 Voltage Protection
962
SIPROTEC 5, Low-Impedance Busbar Protection, Manual
C53000-G5040-C019-C, Edition 04.2021