SIPART DR19
64
C73000-B7474-C140-06
Configuring
Quick Reference
S42
Control signal CB
[0]
1
2
Static, no acknowledgement
Static with acknowledgement
Dynamic as pulse (flip-flop-effect)
S43
Blocking of internal/external setpoint switchover
[0]
1
2
Internal only
External only
No blocking
S44
x-tracking with H or N or Si
[0]
1
No
Yes
S45
Setpoint following CB-failure
[0]
1
Last wi
Safety setpoint SH1
S46
Tracking of wi or SH1/SH2/SH3/SH4 to actual setpoint w
wi
SH1 to SH4
[0]
1
2
yes
no
no
no
yes
yes if S1 = 1
S47
Direction of action in relation to xd (w-x)
[0]
1
Normal (Kp>0)
Reversed (Kp<0)
S48
Connection of D element
[0]
1
2
3
4
xd
x
x1
z direction of action against x (conn. to manipipulated variable y)
z direction of action with x (conn.to manipulated variable y)
S49
Choice of adaptation
[0]
1
2
No adaptation
Control response without overshoot
Control response with overshoot based on absolute value optim.
Config.
switch
Setting
Function
DI
GI
T
A
L
IN
P
U
TS
SETP
O
IN
T SWI
T
C
H
O
VE
R
CO
NT
R
O
L
A
L
G
O
R
IT
H
M