SIPART DR19
60
C73000-B7474-C140-06
Configuring
Quick Reference
Configuring switch list
9
Press button
(13) once (selection level).
10
Press button
(13) once (process control level).
Controller is now in manual mode.
+
NOTE
[ ] reflects the factory setting.
Config.
switch
Setting
Function
S1
Controller type
[0]
1
2
3
4
5
6
7
Fixed setpoint / three-component controller/controller with 2 internal set-
points
Fixed setpoint / three-component controller with 5 internal setpoints
Slave/synchro/SPC controller with internal/external switchover
Ratio controller
Control station / process variable indicator
Program controller (not for types 6DR1901-, 6DR1904-)
Fixed setpoint controller with one setpoint
1)
Slave controller without int/ext switchover
1)
1)
as of software version 3
S2
Output structure
[0]
1
2
3
K-output
S-output:
Two-step controller with 2 outputs heating/cooling
S-output:
Three-step controller for motorized drives, internal
feedback
S-output:
Three-step controller for motorized drives,
external feedback
S3
Mains frequency suppression
[0]
1
50 Hz
60 Hz
S4
Standard input AI1 (I, mV, R, P, T) - Transmitter fault signal
[0]
1
2
3
UNI-input
AI1
min
on sensor breakage
without MUF
UNI-input
AI1
min
on sensor breakage
with MUF
UNI-input
AI1
max
on sensor breakage
without MUF
UNI-input
AI1
max
on sensor breakage
with MUF
S5
Input signal AI1
[0]
1
2
mV (linear), with range plug I [mA] or U [V]
Thermocouple with internal reference junction
Thermocouple with external reference junction
Exit to pro-
cess control
level
BAS
IC
SE
TTIN
G
S
A
N
AL
O
G
I
N
PU
TS