Installation
34
9229 0020 176 0B
2019-04-02
Attachment in the switching cubicle
The vacuum circuit-breaker is delivered in the OPEN switching position and with the
closing spring discharged. Before installing the vacuum circuit-breaker remove the
transport aids (refer to “Unpacking” on page 6).
Checking specifications
Before installation of the vacuum circuit-breaker in a switching cubicle, check the de-
tails on the name plate (see “Name plate” on page 28) in order to avoid confusion.
Installation position
The vacuum circuit-breaker SION
®
can only be installed vertically (to the vacuum
interrupter), as an indoor withdrawable part and as an indoor fixed mounting.
Note
For preliminary work, the vacuum circuit-breaker must be
• secured against falling over,
• placed onto a suitable base or
• prepared for installation while suspended from a crane.
Note
Material damage due to incorrect operation!
If the vacuum circuit-breaker SION
®
is triggered manually with the cover removed
and the mechanical locking device actuated, the operating mechanism of the vac-
uum circuit-breaker will be irreversibly damaged. Any warranty claims are lost in
the event of such incorrect operation.
Use suitable means to prevent the vacuum circuit-breaker SION
®
from closing if
the cover has been removed and the mechanical locking device has been actu-
ated.
Fig. 39
Installation position
Содержание SION 3AE6113-0
Страница 10: ...Transport storage and packing 10 9229 0020 176 0B 2019 04 02 Blank page ...
Страница 44: ...Installation 44 9229 0020 176 0B 2019 04 02 Blank page ...
Страница 50: ...Operation 50 9229 0020 176 0B 2019 04 02 Blank page ...
Страница 54: ...Maintenance 54 9229 0020 176 0B 2019 04 02 Blank page ...
Страница 58: ...58 9229 0020 176 0B 2019 04 02 Blank page ...
Страница 59: ...9229 0020 176 0B 59 2019 04 02 Blank page ...