AFCI Troubleshooting 
Card

For both 1- and 2-pole breakers, 

LED 

indications will appear for 5 seconds each time 
the AFCI is turned "ON" and will display each 
time the beaker is reset for up to 30 days after 
the last trip. The last known trip condition can 
cleared by the following process:
1. Turn the AFCI to the "OFF" position.
2. Press and hold Push-to-Test (PTT) button(s).
3. Turn the AFCI to the "ON" position.
4. Release PTT button(s) within 3 seconds.

1-800-333-7421

 

LED

Test button

LED 1
LED 2

Test  
buttons