Operation
9229 0020 176 0B
47
2019-04-02
Position indicator and spring state indicator when charging the closing
spring, closing and opening
* Spring only charged if motor voltage is applied
Fig. 60
Operating element indicators
First closing operation
If all functions have been checked and are OK, switch on the high voltage while ob-
serving all of the safety regulations and operational requirements.
Charging the closing spring
If the supply voltage is applied, the closing spring is automatically charged by the
motor.
Input
Position indicator
Spring state indicator
Charging
with hand crank,
with motor operat-
ing mechanism
Closing
“CLOSE” pushbut-
ton,
Remote tripping
*
Opening
“OPEN” pushbut-
ton,
Remote tripping
Note
If an undervoltage release 3AX1103… is fitted, it must be connected to control
voltage for switching operations (mechanical or electrical), as otherwise closing
is not possible.
WARNING
Risk of injury if hand cranks other than the original hand crank are used.
When the supply voltage is present, the motor immediately recharges the spring
after a closing operation. If the hand crank does not have a slip coupling, the hand
crank will also rotate.
To avoid injuries caused by the motor starting suddenly, the vacuum circuit-
breaker must be charged only using the original hand crank.
Содержание SION 3AE6113-0
Страница 10: ...Transport storage and packing 10 9229 0020 176 0B 2019 04 02 Blank page ...
Страница 44: ...Installation 44 9229 0020 176 0B 2019 04 02 Blank page ...
Страница 50: ...Operation 50 9229 0020 176 0B 2019 04 02 Blank page ...
Страница 54: ...Maintenance 54 9229 0020 176 0B 2019 04 02 Blank page ...
Страница 58: ...58 9229 0020 176 0B 2019 04 02 Blank page ...
Страница 59: ...9229 0020 176 0B 59 2019 04 02 Blank page ...